N-10Reliability Standards of the North American Electric Reliability Corporation 7/5/2010
5 passages
2. Number: INT-005-2 3. Purpose: To ensure that the implementation of Interchange between Source and Sink Balancing Authorities is distributed by an Interchange Authority such that Interchange information is available for reliability asses...
AI summary This document outlines the purpose of INT-005-2, which is to ensure that interchange information between Source and Sink Balancing Authorities is distributed by an Interchange Authority for reliability assessments.
Example 1 Flow to maintain on Facility 800 MW Expected flow next hour from Transactions using Point-to Point Transmission Service 950 MW Contribution from flow next hour from service to Network customers and Native Load -100 MW Expected Ne...
AI summary The text provides examples of flow calculations on a facility, including expected flows, contributions from service to network customers, net flows, and amounts to be held for reallocation or entered into the Interchange Database (IDC). It also explains the process for handling TLR levels 3b or 5b, involving the Reliability Coordinator and IDC to manage curtailments and flows.
R 2. T he Tr iss ion O to an sm p er a r d Fa i l i Ra ing to te ty t us e on e n c s ha d i f fe fro ho t t w t t er e re n m se i f ie d by Tr iss ion sp ec a an sm o r Ge Ow in he ir to t ne ra r ne r Tr iss ion de l. an sm m o T he Tr...
AI summary The text discusses violations related to transmission service usage, including failure to comply with transmission service obligations, and outlines severity levels for such violations. It references terms like Available Transfer Capability (ATC) and Transmission Reliability Margin (TRM).
Matrix of Violation Risk Factors for Approval Standard Number Requirement Text of Requirement Violation FAC-001-0 R3. The Transmission Owner shall maintain and update its facility connection requirements as required. The Transmission Owner...
AI summary The document outlines a matrix of violation risk factors for approval, focusing on compliance with various reliability standards. It highlights requirements under FAC-001-0 and FAC-002-0, including the need to maintain facility connection requirements and coordinate assessments to ensure compliance with NERC standards.
Matrix of Violation Severity Levels for Approval Standard Number Requirement Number Text of Requirement Lower VSL Moderate VSL High VSL Severe VSL FAC-001-0 R1.2. Transmission facilities, and The Transmission Owner has Transmission facilit...
AI summary The document outlines a matrix defining different levels of violation severity (Lower, Moderate, High, Severe) for transmission facility connection requirements, based on how up-to-date the requirements are with current changes.
07810Quarterly Application for Approval of Reliability Standards of the North American Electric Reliability Corporation - September 2, 2011 9/6/2011
5 passages
2. Violation Severity Levels: Requirement Lower Moderate High Severe R6.4 The Transmission Operator or Balancing Authority has failed to arrange for deliveries of electrical energy or fuel from remote systems through normal operating chann...
AI summary This section outlines the violation severity levels for R6.4, which pertains to the Transmission Operator or Balancing Authority failing to arrange for deliveries of electrical energy or fuel from remote systems through normal operating channels. The severity level for this requirement is categorized as 'N/A' across all levels.
R 7. N / A N / A N / A he iss io d i d T Tr Op to t an sm n er a r no im le i io lan t ts to t p m en re s ra n p fo l lo in is ba in h ic h D tu w g a r nc e w la ks ha be i l iz d B Re tar t t c so ur ce s ve en u e in in he hu do f he t...
AI summary This section discusses violation severity levels related to the Bulk Electric System (BES), Reliability Coordinator (RC), Transmission Operator (TO), and Reliability Coordinator (RRO). It outlines the responsibilities and potential consequences of non-compliance with reliability and operational standards.
2. Violation Severity Levels: R# Lower Moderate High Severe R1 N/A N/A N/A The responsible entity failed to know the status of all generation and transmission resources available for use, even though said information was reported by the Ge...
AI summary This section outlines violation severity levels related to the failure of responsible entities to report and communicate the status of generation and transmission resources to relevant authorities such as the Transmission Operator, Balancing Authority, and Reliability Coordinator.
Matrix of Violation Risk Factors for Information S d d Nu b ta n a r m e r Re ire t q m e n u Nu b m e r Te f Re ire t o t q m e n x u V io la io R is k t n Fa to c r MOD-028-1 R1.5.2. Define if the sink used for ATC calculations is obtain...
AI summary The text presents a matrix outlining violation risk factors for information, specifically focusing on MOD-028-1 and R1.5.2, which relates to defining the sink used for ATC calculations from either the sink field or the Point of Delivery (POD) field of the transmission reservation. The status of this item is listed as 'Pending'.
& lt;sup>4 The voltage schedule is a target voltage to be maintained within a tolerance band during a specified period. Standard Number Requirement Number Text of Requirement Lower VSL Moderate VSL High VSL Severe VSL VAR-001-2 R5. Each Pu...
AI summary The text discusses the voltage schedule, a target voltage to be maintained within a tolerance band during a specified period. It also outlines a requirement (VAR-001-2, R5) for entities to arrange reactive resources to meet their reactive requirements as identified by their Transmission Service Provider, with varying levels of non-compliance severity.