ΔV/V (%) Occurrences
p. p. 13
ΔV/V (%) Occurrences 2.5 ≤ 1 time / hr 2.0 ≤ 5 time / hr 1.0 ≤ 50 time / hr 0.5 ≤ 500 time / hr Dynamic Voltage Changes Must be ≤ 2.5% Section 8.1 of the Nova Scotia Power Utility Service Requirements specifies a maximum of 40 hp for motor...
AI summary The document outlines voltage change limits and motor starting requirements for Nova Scotia Power. Voltage changes must not exceed 2.5%, and motors larger than 40 hp require specific starting methods or utility approval.