N-1-aNotice of Application and Direct Evidence - NSPI - REDACTED (Large File - 59 MB) 3 passages
7.2 Models
7.2 Models NSPI's load forecast is prepared using surveys, econometric and end-use models and assumptions regarding the economic, demographic and technological environment over the forecast period. The total demand for electricity is model...

AI summary NSPI uses surveys, econometric models, and end-use models to forecast load demand across residential, commercial, industrial sectors, exports, and losses. Forecasting procedures have been updated and tested for accuracy, with results shown in the Load Forecast Report and Figure 7.1, which highlights historical performance.

Figure 7.10
Figure 7.10 Ind Industrial Sector Forecast Accuracy Year Forecast GWh Actual GWh % Variance 1998 3,297 3,442 (4.4) 1999 3,497 3,872 (10.7) 2000 3,806 3,930 (3.3) 2001 4,020 3,873 3.7 2002 4,008 3,799 5.2 2003 3,899 4,046 (3.8) 2004 4,120 4...

AI summary Figure 7.10 presents the forecast versus actual GWh for the industrial sector from 1998 to 2005, showing varying levels of accuracy. Figure 7.11 highlights load growth during this period, noting that industrial load growth has averaged 1.4 percent annually over the last five years, influenced by expansions at large customer sites and business closures.

5 7.5.1 System Peak
5 7.5.1 System Peak 6 7 8 9 10 System peak is defined as the highest single hourly average demand experienced in a calendar year. It includes both firm and interruptible load. The system peak forecast is used for operations and generation...

AI summary System peak is defined as the highest single hourly average demand in a calendar year, used for operations, generation planning, and cost allocation. Forecasting involves predicting customer behavior and weather effects. Net System Peak is expected to grow from 2,143 MW in 2005 to 2,639 MW in 2015. Actual peaks in 2005 and 2006 were lower than forecasts due to milder temperatures and industrial shutdowns.

N-1-aAppendix G - Cost of Service Study - REDACTED (Large File - 14 MB) 4 passages
Functionalization
Functionalization The first step in the cost analysis is the functionalization of plant and expenses into the functional groups of production, transmission, distribution and retail. From the books and records of the Company, net plant inve...

AI summary The text describes the initial stage of the cost analysis process, which involves functionalizing plant investments and expenses into four categories: production, transmission, distribution, and retail. While net plant investment and operation and maintenance expenses for production, transmission, and distribution are easily identifiable from the Company's records, certain components of plant, depreciation, and other expenses are not. These specific items must undergo a functionalization process before they can be classified and allocated.

Allocation
Allocation The fourth and final step is the allocation procedure. This step involves applying the allocation factors, determined in step 3, to the classified plant and operating expenses from step 2, to determine the overall cost assigned...

AI summary The text describes the final step of a cost allocation procedure within a Cost of Service Study. This process involves applying specific allocation factors to classified plant and operating expenses to determine the total cost assigned to each service class for a test period. The document references several exhibits detailing rate base analyses, operating costs, depreciation, revenue analysis, allocation factors, and sales/demand data to support the proposed rate structure.

1.2 Methodology
1.2 Methodology The method of cost assignment utilized is the Load Factor/3 Coincident Peak (LF/3 CP) method, as approved by the DARB in its September 29, 1995 Order NSPI-864. This method considers both the demand and energy requirements o...

AI summary The document describes the cost assignment methodology used to allocate generation and transmission responsibilities among different customer classes. It utilizes the Load Factor/3 Coincident Peak (LF/3 CP) method, as approved by the DARB. This approach balances energy requirements (based on system peak load factor) and demand requirements (based on coincident peak demands during the winter months). Additionally, environmental and fuel conversion assets within the rate base are specifically classified as 100% energy-related.

1.2.2 Operating Expense
1.2.2 Operating Expense The analysis of operating costs begins in Exhibit 4 with functionalization. In this step total operating costs are grouped according to production, transmission, distribution, retail and direct. The "Direct Expenses...

AI summary The document describes the methodology for functionalizing and allocating operating expenses within a Cost of Service Study. Operating costs are first grouped into functional categories (production, transmission, distribution, retail, and direct) and then sub-grouped into demand, energy, and customer costs. The analysis specifically details how costs like depreciation, interest, and corporate taxes are assigned to functions, and how demand-related costs are allocated using 3CP demand allocators.

N-1-aAppendix H - Proposed Tariffs (Large File - 21 MB) 1 passage
CBL Base Rate (CBLbr)
CBL Base Rate (CBLbr) This is the CBLbc divided by the energy forecast to be consumed between the UET and the CBL. (In the above example, it is the $286,200 7 4.2 GWh, or $68.14/MWh). APPROVED: NOV A SCOTIA UTILITY AND REVIEW BOARD EFFECTI...

AI summary The document defines the Customer Billing Line base Rate (CBLbr) as the Customer Billing Line base cost (CBLbc) divided by the energy forecast consumed between the Upper ELIIR Threshold (UET) and the CBL. It provides a specific calculation example resulting in a rate of $68.14/MWh. The text notes that this was approved by the Nova Scotia Utility and Review Board for the Nova Scotia Power Incorporated Two Part Real Time Pricing Tariff, which has since been discontinued.

N-1-aAppendix F - Load Forecast Report (Large File - 16 MB) 44 passages
2006 Load Forecast
2006 Load Forecast Prepared September 2006

AI summary The provided text is a heading and a preparation date for a section regarding the 2006 Load Forecast. It does not contain any substantive arguments, data, or analysis beyond identifying the subject matter of the upcoming section.

Preamble
2 3 The Nova Scotia Power Inc. (NSPI) 2006 Load Forecast provides an outlook on the energy and 4 peak demand requirements of in-province customers for 2006 to 2015. As well, it describes the 5 considerations, assumptions and methodology us...

AI summary The Nova Scotia Power Inc. (NSPI) 2006 Load Forecast outlines the projected energy and peak demand requirements for in-province customers from 2006 to 2015. The forecast serves as the foundation for the Company's financial planning and operations. It utilizes methodologies based on sales history, economic indicators, customer surveys, and weather patterns. The report presents a 'most likely' case for rate-making, while also providing high and low scenarios for long-term planning.

Annual Net System Requirement
Annual Net System Requirement In addition to annual energy requirements, NSPI also forecasts the peak hourly demand for future years. The process uses forecast energy requirements and expected load shapes (hourly consumption profiles) for...

AI summary Nova Scotia Power Inc. (NSPI) forecasts the annual net system requirement by combining annual energy requirements with peak hourly demand projections for future years. This process involves applying expected load shapes—derived from historical consumption profiles—to various customer classes. These load shapes are further adjusted based on anticipated changes, such as the installation of major equipment by customers, to determine the growth of the annual net system peak.

Figure 2 Annual Net System Peak (Winter-ending)
Figure 2 Annual Net System Peak (Winter-ending) - 1 Over the longer term, Net System Peak is forecast to increase from 2143 MW in 2005, to 2639 - 2 MW in 2015, which represents an annual growth rate of2.1 percent. - 4 The actual hourly pea...

AI summary The document presents a forecast of the annual net system peak (winter-ending) for Nova Scotia. It notes a historical growth rate of 2.1 percent from 2005 to 2015. The 2006 actual peak was significantly lower than the 2004 record due to a large industrial customer shutdown and a mild winter. The 2007 forecast assumes a return to 30-year average temperatures and explicitly excludes any load reductions from Demand Side Management (DSM) or conservation programs.

1 Introduction
1 Introduction 2 3 NSPI annually develops a forecast of energy sales and peak demand requirements to assess the 4 impact of customer, demographic and economic factors on the future provincial system load. It 5 is a fundamental input to the...

AI summary Nova Scotia Power Inc. (NSPI) produces an annual forecast of energy sales and peak demand requirements to evaluate how demographic, economic, and customer factors influence future provincial system load. This forecast serves as a foundational component for the Company's planning, budgeting, and operations. The specific forecast discussed covers the 10-year period from 2006 to 2015, utilizing data available as of the spring of 2006.

11 Forecast Models
11 Forecast Models 12 13 Nova Scotia electric energy sales are modeled and forecast as three provincial customer sectors: 14 residential, commercial and industrial. Energy forecasts for sector electricity sales are calculated 15 using econ...

AI summary The document describes the methodology for forecasting Nova Scotia's electric energy sales across three sectors: residential, commercial, and industrial. It utilizes multiple linear regression econometric models that correlate electricity consumption with independent variables such as population growth, inflation, GDP, and retail sales. Additionally, individual load survey information is used for large commercial and industrial customers. The models rely on data from the Conference Board of Canada's Economic Outlook to provide a provincial perspective on load growth.

4 Discussion of Major Inputs
4 Discussion of Major Inputs 5 6 The Gross Domestic Product (GDP) for Nova Scotia was $23,528 million (in constant 1997 7 dollars) in 2005, and is forecast to increase by 2.2 percent in 2006 and 2.5 percent in 2007. This 8 growth continues...

AI summary The text provides an economic outlook for Nova Scotia, highlighting projected GDP growth driven by federal military expenditures, retail gains from GST reductions, and major commercial investments like the Dartmouth Crossing and Sydney Tar Ponds clean-up. It notes a cooling housing market, particularly in multi-unit starts, and a slowing Consumer Price Index (CPI). Additionally, the document forecasts stagnant population growth for the province, noting a potential decline by 2010 due to migration to western provinces.

15 Table 1 Forecast Variables
15 Table 1 Forecast Variables Forecast Variables 2005 Actual Growth Rate 2006 Forecast Growth Rate 2007 Forecast Growth Rate N.S. Population 0.02% -0.11% -0.04% N.S. Consumer Price Index 2.8% 2.2% 1.7% N.S. Real Personal Disposable Income...

AI summary The text presents a table of forecast variables for Nova Scotia between 2005 and 2007. It includes historical actual growth rates and projected growth rates for several economic indicators, including population, Consumer Price Index (CPI), Real Personal Disposable Income, Real Gross Operating Product (GOP), and Retail Sales. Additionally, it tracks the forecasted growth rates for real residential heating oil prices.

6 Energy Forecast Details
6 Energy Forecast Details 7 8 For forecasting, modeling and sales reporting, Nova Scotia electric load is divided into three 9 sector requirements: residential, commercial and industrial. The relative sizes of sector sales are 1 0 shown in...

AI summary The document outlines the methodology for forecasting, modeling, and reporting Nova Scotia's electric load. It specifies that the total electric load is categorized into three distinct sector requirements: residential, commercial, and industrial. The relative proportions of sales across these three sectors are illustrated in Figure 3 of the report.

Residential Sector Sales
Residential Sector Sales 25 26 27 In 2005, residential customers represented approximately 36 percent oftotal Nova Scotia energy 28 sales. In addition to direct domestic customers of the Company, the sector also includes 29 residential cus...

AI summary The document describes the methodology for forecasting residential sector electricity sales in Nova Scotia. It highlights that the residential sector, which includes domestic and municipal utility customers, is modeled using an econometric approach. Key variables include retail sales, appliance indices, heating degree-days, and electricity costs. The model accounts for household trends, such as the shift toward smaller households and the impact of appliance efficiency. It notes that while price elasticity exists, it is considered small in the near-term.

Persons per Residential Account
Persons per Residential Account With an ever-increasing array of new technology available, usage per customer continues to grow, despite efficiency improvements for many household appliances. Larger appliances are modeled individually cons...

AI summary The text analyzes factors influencing residential electricity usage, noting that despite appliance efficiency improvements, usage per customer is growing due to new technologies. It highlights that efficiency gains for appliances like televisions and washers are gradual as older models are retired. Additionally, it notes a slight increase in the market share of electric space heating and water heating. The analysis also establishes the methodology for weather-related demand forecasting, using 30-year average heating degree-days (HDD) from Environment Canada data.

Figure 5
Figure 5 95 97 99 01 03 05 07 1 The residential sector load has grown at an average annual rate of 2.3 percent over the past five 2 years or 1.8 percent when adjusted for the effects of weather. Annual residential loads are shown 3 in Figu...

AI summary The document presents data regarding residential sector load growth in Nova Scotia. It notes that the residential sector load has increased at an average annual rate of 2.3 percent over the past five years. When adjusted for weather effects, the growth rate is lower, at 1.8 percent annually. The text refers to Figure 6 for a detailed breakdown of annual residential loads.

Annual Ener gy - Residential Sector
Annual Ener gy - Residential Sector 17 The 2007 load forecast for this sector is 4,327 GWh, or 2.9 percent over the forecast 2006 level. 18 16

AI summary The document provides the 2007 load forecast for the residential sector, estimating a total of 4,327 GWh. This represents a 2.9 percent increase over the previously forecasted 2006 level.

6 Commercial Sector Sales
6 Commercial Sector Sales 8 Energy sales to the commercial sector in 2005 represented 28 percent ofNova Scotia sales. This 9 customer group includes restaurants, hotels, offices, recreational facilities, stores warehouses 10 hospitals, sch...

AI summary The document describes the methodology for forecasting energy sales to Nova Scotia's commercial sector, which accounted for 28 percent of total sales in 2005. The forecast utilizes an econometric model incorporating variables such as real GDP, Real Personal Disposable Income (RPDI), residential electricity sales, and previous year commercial sales. Additionally, the model incorporates direct surveys of large commercial customers to reconcile anticipated load changes by rate class.

Annual Energy- Commercial Sector
Annual Energy- Commercial Sector 13 14 Growth in this sector has averaged 2.6 percent over the past 5 years (2.4 percent when adjusted 15 for weather). Driven by strong wholesale trade, consumer confidence and growth in personal 16 disposa...

AI summary The document analyzes the growth trends of the commercial sector's annual energy usage. Over the past five years, the sector grew at an average rate of 2.6 percent (2.4 percent weather-adjusted), fueled by wholesale trade, consumer confidence, and personal disposable income. Projections for 2006 and 2007 estimate growth rates of 1.6 percent and 2.1 percent, respectively, with an expected average annual growth rate of 2.0 percent over the subsequent 10-year period.

20 Table 3 Commercial Sector Energy
20 Table 3 Commercial Sector Energy Year Commercial Sector GWh Growth Rate % 2000 2,829.4 2.3 2001 2,959.3 4.6 2002 2,996.5 1.3 2003 3,090.6 3.1 2004 3,187.8 3.1 2005 3,223.2 1.1 2006F 3,275.4 1.6 2007F 3,344.6 2.1 2008F 3,423.2 2.3 2009F...

AI summary The text provides historical data on commercial sector energy consumption in Nova Scotia from 2000 to 2015, showing consistent growth. It highlights that the industrial sector, which includes primary resources like mining and forestry and secondary industries like manufacturing, accounted for 36 percent of total electricity sales in 2005. Notably, a small number of large customers account for the majority of the sector's energy load, making the sector's demand highly sensitive to production and technological changes.

Annual Energy – Industrial Sector
Annual Energy – Industrial Sector The load for this sector is forecast using a combination of econometric modeling and large customer surveys. To avoid the effects of customers migrating between the classes, the Small and Medium Industrial...

AI summary The document outlines the forecasting methodology for industrial sector electricity load. Small and Medium Industrial customer loads are forecasted using an econometric model that correlates consumption with GDP, previous year load, and a dummy variable to account for historical migration to the Interruptible Industrial Rate. Conversely, Large Industrial customers are forecasted based on annual surveys regarding planned production levels and equipment changes over a three-year period.

9 Total Sales
9 Total Sales 10 11 Given the combined activities of each sector, including large industrial shutdowns, expansions, 12 etc., total sales grew at an average annual rate of 2.5 percent over the last 10 years. As a result of 13 each of the se...

AI summary The document outlines the historical and projected growth of total electricity sales in Nova Scotia. It notes that total sales grew at an average annual rate of 2.5% over the previous 10 years, influenced by various industrial activities. Looking forward, total sales are projected to grow at an average annual rate of 1.9% over the next 10 years, with billed sales expected to increase from 11,553 GWh in 2005 to 13,944 GWh by 2015.

17 System Losses and Unbilled Sales
17 System Losses and Unbilled Sales 18 19 The load forecast is developed using NSPI "billed" sales rather than "accrued" sales to provide a 20 longer historical time series upon which to base the models. Billed sales refers to the amount o...

AI summary Nova Scotia Power Inc. (NSPI) explains its methodology for developing load forecasts, noting that it utilizes 'billed' sales rather than 'accrued' sales to provide a longer historical time series. The text distinguishes between billed sales, accrued sales, and 'unbilled' sales, which result from billing delays. Additionally, NSPI details system losses, estimating transmission losses at 3.0% of the transmission energy requirement and distribution losses at approximately 6.2% of distribution sales, resulting in an average total system loss of 6.9% of the Net System Requirement (NSR).

16 Table 5 Total Energy Requirement
16 Table 5 Total Energy Requirement Year Net System Requirement GWh Growth Rate % 2000 11,240.1 3.4 2001 11,303.2 0.6 2002 11,501.0 1.8 2003 12,009.1 4.4 2004 12,387.6 3.2 2005 12,338.1 -0.4 2006F 11,784.1 -4.8 2007F 12,980.6 10.5 2008F 13...

AI summary The document presents a historical and forecasted table of the Net System Requirement (NSR) in GWh from the year 2000 to 2015. It outlines the annual growth rates associated with these requirements, showing a general upward trend in energy demand despite some fluctuations in the mid-2000s. The data serves as a basis for understanding historical energy consumption patterns and forecasting future demand.

1 Rate Class Sales
1 Rate Class Sales 2 3 Forecast sales by sector are allocated into 14 rate classes for revenue forecasting purposes. The 4 following section describes these rate classes and their expected energy requirements for the 5 forecast period. In...

AI summary The document explains the methodology for allocating forecast sales into 14 distinct rate classes for revenue forecasting. It notes that while load growth trends are generally driven by sector-wide factors, individual rate class requirements are specifically influenced by customer migration between classes within the same sector. Sales requirements are calculated by combining historical trends, forecast trends, and these migration patterns.

21 Small General
21 Small General 22 23 In the past, this class has comprised commercial sector customers whose annual energy 24 consumption was less than 12,000 kWh. In January 2004, by UARB Order in the fall of 2002, 25 this availability threshold increa...

AI summary The text describes the historical evolution of the 'Small General' customer class, which includes commercial customers with annual energy consumption below a specific threshold. In 2004 and 2005, the UARB increased the threshold from 12,000 kWh/yr to 22,000 kWh/yr and then to 32,000 kWh/yr, respectively. This migration shifted customers from the General class to the Small General class, resulting in significant sales volume growth between 2003 and 2005, with a forecast of 2% annual growth by 2007.

11 Large General
11 Large General 12 - 13 This class compnses large commercial sector customers (malls, universities, hospitals, etc) - 14 whose regular maximum demand is 2,000 kVA or more. As of December 2005, there were 18 - 15 customers in this class re...

AI summary The document defines the 'Large General' customer class, which consists of large commercial sector entities such as malls, universities, and hospitals. Eligibility for this class is based on a regular maximum demand of 2,000 kVA or more. As of December 2005, the class included 18 customers, accounting for 3.6 percent of Nova Scotia Power Inc. (NSPI) sales, with an expected average annual load growth of 1.6 percent over the forecast period.

18 Small Industrial
18 Small Industrial 19 - 20 This class comprises small industrial, farming and processing customers whose regular demand - 21 is less than 250 kV A. This class was made up of 2,212 customers as of December 2005, and had - 22 energy sales r...

AI summary The text defines the 'Small Industrial' customer class, which includes small industrial, farming, and processing customers with a regular demand of less than 250 kV A. As of December 2005, this class consisted of 2,212 customers, accounting for 2.1 percent of Nova Scotia Power Inc.'s total energy sales. Energy requirements for this class are projected to grow at an average annual rate of 2.0 percent throughout the forecast period.

25 Medium Industrial
25 Medium Industrial 26 - 27 This class is applicable to any industrial customer having a regular demand of at least 250 kV A, - 28 but less than 2,000 kV A. As of December 2005, there were 225 customers in this class, - 29 representing ab...

AI summary The text defines the 'Medium Industrial' customer class for Nova Scotia Power Inc. (NSPI). This class applies to industrial customers with a regular demand between 250 kVA and 2,000 kVA. As of December 2005, there were 225 customers in this category, accounting for approximately 4.8 percent of total NSPI sales. The class is projected to experience an average annual sales growth of 2.0 percent over the subsequent 10-year period.

1 Unmetered Services
1 Unmetered Services 2 - 3 This class comprises street and area lighting, as well as miscellaneous lighting and small loads. - 4 In 2005, unmetered sales represented approximately 0.9 percent of total NSPI sales. Energy - 5 sales in this c...

AI summary This section defines the 'Unmetered Services' class, which includes street and area lighting, miscellaneous lighting, and small loads. Historical data indicates that in 2005, unmetered sales accounted for approximately 0.9 percent of total Nova Scotia Power Inc. (NSPI) sales. The forecast for energy sales within this specific class projects an average annual growth rate of 2.0 percent over the forecast period.

5 Peak Demand
5 Peak Demand 6 7 The Total System Peak is defined as the highest single hourly average demand experienced in a 8 year. It includes both firm and interruptible loads and due to the weather-sensitive load 9 component in Nova Scotia, the Tot...

AI summary The document defines the Total System Peak as the highest single hourly average demand in a year, typically occurring between December and February in Nova Scotia due to weather-sensitive loads. It details the methodology for forecasting Net System Peaks, which involves using forecast monthly energies and historical coincident load factors for most rate classes, while individual demand contributions for large customers are assessed based on specific history. The system peak for 2007 is forecast at 2256 MW, with a projected long-term growth rate of 2.1 percent by 2015.

Residential Sector Econometric Model Detail
Residential Sector Econometric Model Detail DOMENG = 683.4 \text{ AIDX} + 0.1257 \text{ CHDD} - 31.79 \text{ RREP} + 0.07877 \text{ RRTS} + 0.4599 \text{ DOMENG}_{-1}

AI summary The document provides the specific mathematical formula for the DOMENG variable within the residential sector econometric model. This variable is calculated using a weighted combination of several factors, including appliance saturation and average use (AIDX), heating degree-days (CHDD), average sector customer price per kWh (RREP), retail sales (RRTS), and its own lagged value from the previous period (DOMENG_-1).

Forecast Model for DOMENG Regression (5 regressors, 0 lagged errors)
Forecast Model for DOMENG Regression (5 regressors, 0 lagged errors) Term Coefficient Std. Error t-Statistic Significance EFFIDX 683.420493 74.620566 9.158608 1.000000 CUSTHDD 0.125711 0.035709 3.520432 0.998811 RREP -31.791492 5.282988 -6...

AI summary The document presents a forecast model for the Demand Oriented Modeling Energy Generation (DOMENG) regression analysis. The model utilizes five regressors with zero lagged errors to determine the significance of various economic and environmental factors. Key variables include an energy efficiency index (EFFIDX), customer heating degree-days (CUSTHDD), average sector customer price (RREP), and retail sales (RRTS). The statistical table provides coefficients, standard errors, t-statistics, and significance levels for each term within the sample.

Section 59
MAD 34.81 Sample size 41 Mean 2499 R-square 0.9984 Durbin-Watson 1.523 Forecast error 46.15 Mumber of parameters 5 Standard deviation 1096 Adjusted R-square 0.9982 Ljung-Box(18)=18.36 P=0.5681 BIC 54.23 RMSE 43.24

AI summary The provided text presents statistical output for a regression analysis, likely used in forecasting or modeling for the regulatory proceeding. It includes a sample size of 41, a mean of 2499, and an R-square value of 0.9984, indicating a very high level of correlation. Other metrics provided include a forecast error of 46.15, a standard deviation of 1096, and a Bayesian Information Criterion (BIC) of 54.23.

Residential Model Input Variables and Contributions
Residential Model Input Variables and Contributions Year AIDX AIDX Contrib. CHDD CHDD Contrib. Electric Price Electric Price Contrib. Retail Sales Retail Sales Contrib. DomEng[-1] DomEng[-1] Contrib. Nat. Gas Effect DomEng\ Actual Growth G...

AI summary The document provides a historical data table (1994–2015) detailing residential model input variables and their respective contributions to total electricity demand. Key variables analyzed include the Energy Efficiency Index (AIDX), Composite variable for all-electric customers and heating degree-days (CHDD), Electric Price, and Retail Sales. The data tracks trends in growth, actual demand, and the impact of factors like the 'Nat. Gas Effect' and 'DomEng' (Demand Oriented Modeling Energy Generation) to align forecasts with historical actuals.

Commercial Sector Econometric Model Detail
Commercial Sector Econometric Model Detail • Commercial Sector Ec monitorite model Detail 2 3 4 4 5 COMENG = 0.018 38 RQTOS + 0.0196 68 RPDI + 0.201. 5 DOMENG + 0.51 45 COMENG-1 6 9 Forecast Model for ad ammana) 6 7 8 9 Regression(4 regre...

AI summary The document details a regression-based econometric model used to forecast commercial sector electricity demand. The model utilizes several key variables, including Real Quarters to Sales (RQTOS), Real Personal Disposable Income (RPDI), and Demand Oriented Modeling Energy Generation (DOMENG), alongside a lagged commercial energy consumption variable (COMENG[-1]). The model demonstrates high predictive accuracy with an R-square of 0.9983. It also includes a 7.0 GWh launch adjustment applied between 2005 and 2015 to align forecasted figures with actual historical data.

Industrial Econometric Model Details
Industrial Econometric Model Details Small and Medium Industrial Classes are summed and modeled together. SM_{IND} = 0.009305 RQTOS + 0.7441 SM IND_{-1} - 28.69 MIGRATE

AI summary The document describes the econometric modeling used to forecast demand for Small and Medium Industrial customer classes. It specifies that these classes are aggregated for modeling purposes. The model for these classes is defined by a regression equation incorporating Real Quarters to Sales (RQTOS), the previous period's Small and Medium Industrial demand (SM IND_-1), and a migration factor (MIGRATE).

Forecast Model for SM IND Regression(3 regressors, 0 lagged errors)
Forecast Model for SM IND Regression(3 regressors, 0 lagged errors) Term Coefficient Std. Error t-Statistic Significance MIGRATE RQTOS SM_IND[-1] -28.699063 0.009305 0.744101 6.694597 0.002628 0.083565 -4.286899 3.540010 8.904460 0.999745...

AI summary The document presents a regression analysis for forecasting the Small and Medium Industrial (SM_IND) electricity demand. The model utilizes three regressors with zero lagged errors. The primary independent variable identified in the table is the 'MIGRATE RQTOS SM_IND[-1]' term, which shows a negative coefficient of -28.699063 and is statistically significant at the 0.002628 level. The section focuses on the statistical parameters including coefficients, standard errors, t-statistics, and significance levels for these variables.

Section 64
20 21 Sample size 27 Number of parameters 3 22 23 24 25 Mean 566 Standard deviation 125.4 Adjusted R-square 0.9855 \ Ljung-Box(18)=33.36 P=0.9849 BIC 17.1 RMSE 14.24 R-square 0.9866 Durbin-Watson 1.022 Forecast error 15.11 26 MAPE 0.01931...

AI summary The provided text contains statistical performance metrics for a forecasting model, likely used for energy demand or load projection. It reports a mean of 566 with a standard deviation of 125.4. The model demonstrates high accuracy with an Adjusted R-square of 0.9855 and a Mean Absolute Percentage Error (MAPE) of 0.01931. Statistical tests, including the Ljung-Box test and Durbin-Watson statistic, are included to validate the model's reliability and lack of autocorrelation.

1 Industrial Model Input Variables and Contributions
1 Industrial Model Input Variables and Contributions 2 3 Year RQTOS RQTOS contrib GWh MIGRATE MIGRATE contrib GWh SM_Indt·11 SM_Indt·11 contrib GWh SM_Ind\ GWh GWh Actual Growth % 1994 17,535 163.2 1 -28.7 517.8 385.3 519.7 528.3 2.0 1995...

AI summary The document presents a historical analysis of industrial model input variables and their contributions to the Net System Requirement (NSR) in Gigawatt-hours (GWh) from 1994 to 2015. Key variables discussed include Real Quarters to Sales (RQTOS), MIGRATE, and Small and Medium Industrial (SM_Ind) metrics. The data tracks the growth and contribution of these factors to the total GWh, providing a basis for the 2006 Nova Scotia Power Inc. (NSPI) energy requirement forecast.

3
3 Residential Commercial Industrial Total Total Year Sector Growth Sector Growth Sector Growth Sales Growth Losses Energy Growth GWh % GWh % GWh % GWh % GWh GWh % 1994 3,498 0.4 2,660 1.0 2,756 0.3 8,914 0.5 679 9,593 0.0 1995 3,463 -1.0 2...

AI summary The provided text is a data table titled 'Coincident Peak Demand- 2006 NSPI Forecast'. It details historical electricity sales, growth percentages, and energy growth across three sectors (Residential, Commercial, and Industrial) from 1994 to 2015. The data tracks total sales in GWh, showing a steady upward trend in total sales and energy growth over the 21-year period, despite fluctuations in individual sector growth rates.

3 Peak Forecast
3 Peak Forecast Year Net System Peak MW Growth % Non-Firm Peak MW Growth % Firm Peak MW Growth % 2000 2009 6.6 412 33.3 1597 1.3 2001 1988 -1 369 -10.4 1619 1.4 2002 2078 4.5 348 -5.7 1730 6.9 2003 2074 -0.2 291 -16.4 1783 3.1 2004 2238 7....

AI summary The document provides a historical overview of peak electricity demand in Nova Scotia from 2000 to 2015. It tracks three distinct categories: Net System Peak MW, Non-Firm Peak MW, and Firm Peak MW. The data illustrates varying growth rates over the 15-year period, with Net System Peak showing significant fluctuations and Firm Peak demonstrating a steady upward trend of approximately 1.3% to 3.1% annually in the early 2000s before stabilizing.

4
4 Class Sales (GWh) 2002 Actual 2003 Actual 2004 Actual 2005 Actual 2006 2007 Residential 3,760 3,940 4,040 4039 4130 4251 Small General 104 109 165 232 237 242 General Demand 2,350 2,417 2,426 2381 2424 2476 Large General 358 375 401 413...

AI summary The provided text consists of a data table detailing Class Sales in Gigawatt-hours (GWh) from 2002 to 2007. It breaks down sales by customer class, including Residential, Small General, General Demand, Large General, Unmetered, Small Industrial, Medium Industrial, Large Industrial, RTP, L.l. Interruptible, Mersey System, Mersey Additional Energy, GR&LF, Municipal, Ind. Expansion Rate, and ELII Rate. The table also tracks Losses & Unbilled amounts and the Net System Requirement (NSR) for the same period.

Appendix C
Appendix C High and Low Forecast Scenarios

AI summary The provided text is a heading for Appendix C of a regulatory proceeding, indicating that the subsequent section will contain high and low forecast scenarios. No specific arguments, data, or entities are discussed in this specific fragment.

High and Low Forecast Scenarios
High and Low Forecast Scenarios Low Forecast Scenario Assumptions 1 1, 700 GWh lyr from 2007 onward) Major Paper Mill Closure(- 2 Economic Growth Diminishes (Base case growth rate decreases by 50%) 3 45% reduction in home heating oil price...

AI summary The document outlines two extreme forecast scenarios—High and Low—to test the sensitivity of the 2006 Load Forecast. The Low Forecast assumes diminished economic growth, major paper mill closures, lower heating oil prices, and reduced residential customer additions. Conversely, the High Forecast assumes improved economic growth, new industrial load additions, significant heating oil price increases, and higher residential customer growth. The tables provide year-over-year projections for Net System Requirement (NSR) and Peak demand in GWh and MW from 2007 to 2015 under these varying assumptions.

Appendix D
Appendix D Forecast Sensitivity by Major Variable

AI summary The provided text is a heading for Appendix D, which introduces a section regarding 'Forecast Sensitivity by Major Variable.' The content does not contain specific data, arguments, or analysis, as it serves only as a structural placeholder for subsequent sensitivity analysis within the regulatory proceeding.

5 Based upon the 2006 load forecast models, the following table shows the relative sensitivity of 6 the forecast to changes in various input assumptions.
5 Based upon the 2006 load forecast models, the following table shows the relative sensitivity of 6 the forecast to changes in various input assumptions. Variable Assumed Change Effect on 2007 Load GWh Effect on 2011 Load GWh Lagged Depend...

AI summary The document presents a sensitivity analysis of the 2006 load forecast models, quantifying the projected impact of various input variables on electricity load for the years 2007 and 2011. Key drivers analyzed include economic indicators (GDP, Retail Sales, Real Disposable Income), residential and commercial demand factors (customer additions, electricity price), and environmental/climatic conditions (Heating Degree-Days, Heating Oil Price). The data highlights that Retail Sales and GDP have the most significant long-term impacts on the 2011 forecast.

Section 79
9 Note: This table portrays changes to individual variables only. In many cases, there are interdependencies that 1 0 would require scenario development for more complete evaluation. 11

AI summary The provided text is a brief note regarding a table of variables. It clarifies that the table only illustrates changes to individual variables and acknowledges that interdependencies between these variables exist. The author notes that a full scenario development would be necessary for a more comprehensive evaluation of these interdependencies.

N-1-aAppendix B - Operating, Maintenance and General Expenses - REDACTED (Large File - 12 MB) 1 passage
(in Thousands of $)
(in Thousands of $) 2005 Actual 2006 Compliance 2006 Forecast 2007 Forecast 2007 Fct. Vs. 2005 Actual 2007 Fct. Vs. 2006 Compliance 2007 Fct. Vs 2006 Fct > Travel decrease due to a reduction in anticipated travel and use of more teleconfer...

AI summary The document provides a detailed variance analysis of corporate operating expenses, specifically focusing on the 2007 forecast compared to 2005 actuals and 2006 compliance figures. Key drivers for cost decreases include reduced travel through teleconferencing, the transfer of the PeopleSoft contract to the IT department, and lower training requirements. Conversely, costs for contracts increased due to succession planning, workforce training (including Nova Scotia Community College programs), and the Employee Assistance Program (EAP).

N-1-aAppendix A - Financial Tables - REDACTED 2 passages
2007 Financial Outlook
2007 Financial Outlook 2 (1) (2) (3) Compliance Rates Test Year (4) Present Rates Test Year (5) Proposed Rates Test Year Actual 2005 Forecast 2006 Forecast 2006 Forecast 2007 Forecast 2007 3 Corporate Groups 4 Power Production 5 Customer O...

AI summary The document presents a financial outlook table for the year 2007, comparing compliance rates across three distinct categories: Actual 2005, Forecast 2006, and Forecasts for 2007. The data is structured to show the financial performance and projections for Corporate Groups, Power Production, and Customer Operations/Services. The table serves as a comparative tool to evaluate historical performance against future rate test year projections.

2007 Financial Outlook
2007 Financial Outlook 2 Test Year Forecast 2007 3 Forecast Net Earnings at Proposed Rates (Full Year) $99.4 4 5 Less: 6 Net earnings at present rates 48.3 7 Incremental other revenue increase 0.4 8 Mersey Additional Energy revenue increas...

AI summary The document presents a financial outlook for the 2007 test year, detailing the projected net earnings at proposed rates compared to present rates. It identifies a forecast net earnings of $99.4 million at proposed rates, with a significant component being a $31.5 million net increase in income tax. The analysis calculates an Electric Revenue Rate Requirement of $81.3, resulting in a 7.5% projected percent increase on present rates for general application customers.

N-2-aRIRs 40 to 69 - NSUARB to NSPI - REDACTED (Large File - 34 MB) 14 passages
Section 107
January 1, 2006 to December 31, 2006 - Projection for 2006

AI summary The provided text is a brief heading or reference indicating a projection period for the year 2006, spanning from January 1, 2006, to December 31, 2006.

Response IR-44:
Response IR-44: - a) Yes, the 2008 Operating, Maintenance and General (OM&G) projection shown in Appendix C includes increased funding to cover the referenced initiatives. - b) Multi year forecasts of OM&G costs are not relevant to establi...

AI summary Nova Scotia Power Inc. (NSPI) responds to an information request regarding the 2008 Operating, Maintenance and General (OM&G) projections. The company confirms that the 2008 projections include increased funding for specific initiatives. However, NSPI argues that multi-year OM&G cost forecasts are not relevant for establishing the 2007 test year revenue requirement, asserting that such estimates are inherently uncertain and subject to significant future variation.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: UARB Response IR-46: (cont'd) The difference between billed sales and the energy actually consumed is referred to as "unbilled sales". The unbilled sales level varies due to growth rates, weat...

AI summary The Utility Analysis and Regulatory Board (UARB) provided a response to Information Request IR-46 for Nova Scotia Power Inc. (NSPI). The text defines 'unbilled sales' as the difference between energy actually consumed and energy billed. It notes that unbilled sales fluctuate based on factors such as growth rates and weather, and specifies that the 9.7 GWh increase in unbilled sales for 2007 was apportioned across seven accrued classes based on their relative size as a percentage of total billed sales.

Question IR-4 7: Reference Pages 153-156.
Question IR-4 7: Reference Pages 153-156. Please explain in a bit more detail how one moves from Total Requirements to System Peak. As part of this explanation, please address the following points: - a. the separation of annual sales as fo...

AI summary The document contains a formal Information Request (IR-4 7) seeking a detailed explanation of the methodology used to transition from Total Requirements to System Peak. The requester specifically asks for clarification on four components: the separation of annual forecast sales into rate classes, the development of monthly sales and coincident load factors, the calculation of System Peak, and the distinction between non-firm and firm coincident peaks. The requester also requests illustrative calculations for the years 2005 and 2007, including all underlying assumptions.

Response IR-47: This procedure was outlined in the Company's response to Information Requests in the 2006 Rate Case.
Response IR-47: This procedure was outlined in the Company's response to Information Requests in the 2006 Rate Case. a. The year 2005 sales data used in the forecast are the actual yearend sales, including by rate class. For the forecast,...

AI summary Nova Scotia Power Inc. (NSPI) provides details on its sales data and forecasting methodology for the rate case. The company utilizes 2005 year-end actual sales data, segmented by rate class. While municipal class sales account for less than 2% of total in-province sales, NSPI's sector sales models incorporate all provincial loads, including municipal utilities. The municipal class is further broken down by residential, commercial, and industrial components, with individual customer forecasts based on recent trends.

industrial sector growth rate is not used since it tends to fluctuate more than is observed within the municipalities.
industrial sector growth rate is not used since it tends to fluctuate more than is observed within the municipalities. NS Sector GWb Totals: Sector Growth Rates: Year Dom+ Domestic Commercial Industrial Domestic Commercial Com Industrial 2...

AI summary The text provides a comparative analysis of electricity sales and growth rates across different sectors, specifically noting that industrial sector growth rates are excluded from certain calculations due to high volatility compared to municipal trends. It presents data on domestic, commercial, and industrial sales from 2005 to 2007, alongside municipal sales distribution. Additionally, it outlines the forecasting methodology for the Residential Time-Of-Use (ETS) class, which relies on customer forecasts and average use per customer due to small sample sizes and similar load characteristics.

Regular Residential class sales are then calculated by subtracting the ETS sales and the residential component of the Municipal class sales from the sector sales forecast.
Regular Residential class sales are then calculated by subtracting the ETS sales and the residential component of the Municipal class sales from the sector sales forecast. Year Residential Sector GWh Municipal Res. Component GWh Residentia...

AI summary The text outlines the methodology for forecasting electricity sales across various customer classes. Regular Residential class sales are derived by subtracting ETS and Municipal residential components from the total sector forecast. Small General class sales are projected using a 2 percent annual growth rate, accounting for recent load growth from customer migration due to rate class threshold changes. Large General class sales are based on individual customer surveys, while Unmetered class sales follow the overall commercial sector growth rate.

Response IR-47: (cont'd)
Response IR-47: (cont'd) Year Large General GWh Unmetered GWh Unmetered Growth Rate 2005 412.8 108.2 3.0% 2006F 413.3 109.9 1.6% 2007 421.4 112.3 2.1 % General sales are then calculated as the Commercial sector sales minus the Small Genera...

AI summary The text provides a breakdown of electricity sales data for the Commercial sector, specifically detailing the calculation methods for 'General' sales. It outlines how General sales are derived by subtracting Small General, Large General, Unmetered, and Municipal commercial components from total Commercial sector sales. Additionally, it describes the methodology for forecasting Small and Medium Industrial class sales using an econometric model and historical growth rates.

Response IR-47: (cont'd)
Response IR-47: (cont'd) Year Small & Medium Industrial Growth Rate Small Industrial GWh Medium Industrial GWh 2005 -1.0% 241 .1 557.1 2006F 2.4% 247.0 570.7 2007 2.4% 253.0 584.6 The Industrial sector load is equal to the sum of the Indus...

AI summary The document provides historical and forecasted load data for the industrial sector, categorized by small, medium, and large industrial components, as well as municipal components. It details growth rates and gigawatt-hour (GWh) consumption from 2005 to 2007. Additionally, it explains the methodology for calculating accrued sales, which utilizes a 5-year historical average of monthly rate class sales as a percentage of the annual total.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: UARB Response IR-47: (cont'd) For the large customer classes, the monthly sales are based on recent load profiles and results of customer surveys which may indicate any planned outages, expans...

AI summary The Utility Analysis and Regulatory Board (UARB) is providing a response to an Information Request (IR-47) for Nova Scotia Power Inc. (NSPI). The text specifies that monthly sales for large customer classes are determined by analyzing recent load profiles and customer surveys to account for planned outages, expansions, or typical monthly load variations. It introduces a table containing the 2007 forecast monthly class sales in Gigawatt-hours (GWh).

Class Sales
Class Sales (GWh) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Lg. General 36.7 33.0 35.6 32.9 33.0 33.1 37.2 38.9 35.3 35.5 34.6 35.6 Lg. Ind. Firm 11.7 10.8 11.3 11.2 11.6 11.3 11.9 12.0 11.5 11.5 11.2 11.5 Lg. Ind. Interrupt. 18.5 17...

AI summary The document provides a detailed breakdown of monthly electricity sales in Gigawatt-hours (GWh) across various rate classes, including Large General, Large Industrial Firm, Mersey, and Municipal. It also describes the methodology for developing monthly coincident load factors, which are derived from actual rate class load profiles and monthly peak data. Specifically, it notes an assumption for the ELIIR peak load based on average monthly coincident demand observed in 2005.

Section 193
In the case of actual data for 2005, monthly system peak is determined from the SCADA data. Hourly load data is collected for large customers (greater than 2 MV A), which includes all customers on non-firm rates. The non-firm coincident pe...

AI summary The text describes the methodology used to determine monthly system peak and coincident peak loads for the year 2005 using SCADA data. It explains the process for calculating non-firm coincident peak by summing customer loads on non-firm rates at the hour of the monthly system peak, including estimated losses. Conversely, the firm coincident peak is derived by subtracting the non-firm coincident peak from the total system peak, specifically referencing data from January 2005.

Question IR-62: Reference Appendix B, Page 33. It is stated that:
Question IR-62: Reference Appendix B, Page 33. It is stated that: "Labour decrease due to reductions in paid time off, safety and general business meetings, the transfer of apprentice program costs, and transfers to the Control Centre part...

AI summary The Information Request (IR-62) seeks detailed cost data and qualitative discussions regarding specific factors influencing labor cost trends. The request asks for 2007 cost levels and explanations for labor decreases caused by reduced paid time off and business meetings, the transfer of apprentice program costs, and transfers to the Control Centre. Conversely, it seeks to understand the costs associated with an increase in reactive line maintenance work, noting these factors partially offset each other.

Question IR-63: Reference Appendix B, Page 33. It is stated that:
Question IR-63: Reference Appendix B, Page 33. It is stated that: "Materials increase due to additional streetlight and service repairs, and aligning forecast with actual trending for system maintenance." - a. Please provide 2007 costs ass...

AI summary The Information Request (IR-63) seeks clarification on the specific cost components of material increases mentioned in Appendix B, Page 33. The Board is requesting the 2007 costs specifically for streetlight and service repairs. Additionally, the Board requires a discussion on Nova Scotia Power Inc.'s (NSPI) level of responsibility for service repairs and a detailed explanation of the 2007 costs incurred to align system maintenance forecasts with actual trends.

N-2-bRIRs 70 to 75 - NSUARB to NSPI - REDACTED (Large File - 33 MB) 1 passage
Response IR-72: (cont'd)
Response IR-72: (cont'd) - b. Information available to mid-April 2006 was used in the forecast, with the exception of a September 2006 home heating oil price forecast for the years 2008-2015. - c. The economic data series used in the forec...

AI summary The response provides details on the data and methodology used in a forecast, including the use of economic data from February 2006, heating oil price forecasts, and load growth calculations. It also references the Public Utilities Act and an application by Nova Scotia Power Incorporated for rate revisions.

N-2-bRIRs 77 to 84 - NSUARB to NSPI - REDACTED (Large File - 35 MB) 5 passages
Section 43
The health care cost trend significantly influences the amounts presented for health care plans. An increase or decrease of one percentage-point of the assumed health care cost trend would have the following impact in 2005:

AI summary The text addresses the sensitivity of health care plan cost projections to the assumed health care cost trend. It notes that fluctuations in this trend significantly influence the total amounts presented, specifically highlighting that even a one percentage-point change in the assumed trend would have a measurable impact on the 2005 figures.

(millions of dollars) 2006
(millions of dollars) 2006 Impact of increasing the rate of return assumption by 0.5% Benefit cost Accrued benefit asset $(2.9) $2.9 Impact of increasing the discount rate assumption by 0.5% Benefit cost Accrued benefit asset $(6.4) $6.4 T...

AI summary The document outlines the financial impacts of adjusting the rate of return and discount rate assumptions by 0.5% on benefit cost accrued benefit assets for the year 2006. It specifies that the discount rate is based on 'A' grade long-term Canadian corporate bonds with a duration matching the accrued benefit obligation. The expected discount rate for 2006 is projected at 5.25%, down from 6.0% in 2004 and 2005.

2. Seasonal Nature of Operations
2. Seasonal Nature of Operations Interim results are not necessarily indicative of results for the full year due primarily to seasonal factors. Sales and related production vary significantly over the year, with Q1 and 04, the strongest pe...

AI summary The text explains that interim financial results are not necessarily representative of full-year performance due to the seasonal nature of the utility's operations. It highlights that sales and production levels fluctuate significantly throughout the year, peaking during the first and fourth quarters (Q1 and Q4) because of increased demand driven by colder winter weather and reduced daylight hours.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: UARB Question IR-83: Please provide the load forecast information used as input to the Strategist run, including monthly peak demand, monthly energy requirements and the typical week used for...

AI summary The Nova Scotia Utility and Rate Board (UARB) provided a response to an information request (IR-83) from Nova Scotia Power Inc. (NSPI). The response includes the load forecast data used for the Strategist run, specifically detailing 2007 monthly energy requirements and peak demand. The UARB provided this data in multiple formats, including a tabular 168-hour typical week and supporting graphical representations.

Hourly Loads for a Typical Week - 2007 Forecast
Hourly Loads for a Typical Week - 2007 Forecast Day-Hour Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Mon 12:00 AM 1557.2 1457.5 1394.4 1355.8 1186.4 1186.6 1159.2 1185.6 1095.2 1187.0 1376.3 1418.4 Mon 1:00 AM 1537.0 1417.3 1378.3 1309...

AI summary The document provides a detailed hourly load forecast for a typical week in 2007, broken down by month. The data illustrates electricity demand patterns across a 24-hour cycle, showing peak usage periods (typically between 7:00 AM and 10:00 AM) and lower off-peak demand during late-night and early-morning hours. The values fluctuate seasonally, with notable variations between winter months and the summer period.

N-2-bRIR 76 - NSUARB to NSPI - REDACTED (Large File - 46 MB) 1 passage
Preamble
The expected return on plan assets is based on management's best estimate of future returns, considering economic and consensus forecasts . The 2004 and 2005 benefit cost calculations assumed that plan assets would earn a rate of return of...

AI summary The text outlines the methodology for determining the expected return on plan assets, noting that management uses best estimates based on economic and consensus forecasts. It specifically identifies that the benefit-cost calculations for 2004 and 2005 utilized assumed asset return rates of 7.5% for Nova Scotia Power Inc. (NSPI) and 8.0% for Bayonne Holding Enterprises (BHE), with the 2006 calculation expected to maintain these same assumptions.

N-2-cRIRs 1 to 66 - Avon to NSPI - REDACTED (Large File - 13 MB) 1 passage
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: AVON Question IR-42: Please provide the price curves and information that NSPI used to produce a "consensus forecast" for imported coal prices as referred to in NSPI Direct Testimony, p. 57. R...

AI summary AVON is requesting information on the price curves and data used by NSPI to create a 'consensus forecast' for imported coal prices, as mentioned in NSPI Direct Testimony. The response directs AVON to refer to Liberty IR-64 for the requested information.

N-2-cRIRs 1 to 39 - CA to NSPI - REDACTED (Large File - 14 MB) 8 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CA Question IR-11: The Bank of Canada, at http://www.bankofcanada.ca/ en/rates/ can_ us_ close.html, shows monthly closing rates for Can$/US$ ranging from a high of $1.1937 on November 14, 200...

AI summary Canada Nova Scotia Electricity Corporation (CA) responded to an information request from Nova Scotia Power Inc. (NSPI) regarding the currency exchange rate forecast. CA corrected a discrepancy in NSPI's evidence, clarifying that the percentage of the 2007 dollar requirement subject to the blended rate of 1.19 should be 80 percent rather than the 70 percent previously stated in the evidence.

NSPI's average foreign rates are developed as follows:
NSPI's average foreign rates are developed as follows: (in millions) 2007 USD Requirement $376 Forecasted USD proceeds from long- ($104) term receivable Net USD requirement $272 Hedged (see CA IR-11 Attachment 1) $228 $1.1853 Unhedged $44...

AI summary The document outlines the development of Nova Scotia Power Inc.'s (NSPI) average foreign rates for 2007. It details the calculation of the net USD requirement by subtracting forecasted proceeds from long-term receivables from the total USD requirement. The requirements are categorized into hedged and unhedged portions, with the unhedged requirements based on average 2007 forecasts provided by major banks.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CA Question IR-13: Identify any revenue items forecast for 2007 that did not exist in 2006, or which are not expected to exist in 2008, at approximately the same level as in 2007. Response IR-...

AI summary Canada Nova Scotia Electricity Corporation (CA) responded to an information request from Nova Scotia Power Inc. (NSPI) regarding revenue forecasts. CA stated that all revenue items forecasted for 2007 were present in 2006 and are projected to continue in 2008. CA noted that the specific revenue levels for 2008 will be determined by the approved rates and the projected load for that year.

Response IR-17: (cont'd)
Response IR-17: (cont'd) d. Please refer to UARB IR-51d. NSPI is not able to estimate when the costs will be known as it is dependent on subsequent Board decisions. DATE FILED: November 20, 2006 CA IR-17 Page 2 of2

AI summary Nova Scotia Power Inc. (NSPI) states that it is currently unable to provide an estimate for specific costs because they are contingent upon future decisions made by the Utility Advice and Rate Board (UARB). The response refers the reader to UARB IR-51d for further context regarding these pending costs.

Response IR-18 (cont'd):
Response IR-18 (cont'd): - a. The use of a forward test year is not considered a form of protection, although the use of a historic test year would tend to increase regulatory risks. A future test year has been assumed by Dr. Morin. - b. T...

AI summary The text addresses the methodology used in a cost-of-service assessment, specifically focusing on the selection of test years and the inclusion of costs in forecasts. It argues that using a forward test year does not constitute a form of protection, unlike a historic test year which would heighten regulatory risk. Furthermore, it clarifies that including costs in a test year forecast is a standard regulatory procedure, and the assessment assumes that all prudent costs are included without assuming a denial of cost recovery.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CA Question IR-20: Please provide the NSPI load forecast for 2007 assuming that DSM is implemented along the lines of the company's DSM proposal and associated budget. Response IR-20: The incl...

AI summary Canada Nova Scotia Electricity Corporation (CA) responded to an information request regarding Nova Scotia Power Inc.'s (NSPI) load forecast for 2007. CA stated that because Demand Side Management (DSM) is integrated into the Integrated Resource Plan (IRP) with a specific timetable, it is not possible to implement NSPI's specific proposal in a manner that would achieve the anticipated year-one DSM effects by 2007.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CA Question IR-21: In reference to Appendix F, the Load Forecast, at p. 30, the detail of the residential load forecast algorithm, please explain the column CHDD. If this refers to heating deg...

AI summary In response to an information request regarding the residential load forecast, Canada Nova Scotia Electricity Corporation (CA) clarifies the 'CHDD' variable used in the model. CA explains that CHDD represents growth in space heating load, calculated by multiplying the estimated number of customers with electric space heat by annual heating degree-days (HDDs). While the model assumes constant HDDs based on normal weather, the CHDD variable is forecast to increase due to a projected rise in the number of customers using electric space heating.

6.7.3 Findings
line on the expenditures to see whether or not what would happen if you did eliminate some or reduce some or make certain restructuring in your operation. Was that type of an exercise carried out? - A. (Biunden) It has been over a number o...

AI summary The testimony addresses Nova Scotia Power Inc.'s (NSPI) Other Management and General (OM&G) costs. Mr. Blunden asserts that NSPI has consistently applied a rigorous approach to managing these costs over several years, and that all current opportunities for reduction have been reflected in the application without compromising service. He disputes the recommendation by PriceWaterhouseCoopers (PWC) to provide detailed five-year multi-year forecasts of OM&G spending, questioning the merit of such an exercise.

N-2-dRIRs 1 to 46 - CME to NSPI - REDACTED (Large File - 18 MB) 20 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-6: Reference Page 8, Lines 3-5 Provide a detailed explanation and a lmancial breakdown (for the total of the estimated $19.6 million) explaining how increased load results in t...

AI summary CME responded to a request for information regarding the financial breakdown of the estimated $19.6 million in costs resulting from increased load between 2006C and 2007. The response directs the inquirer to specific calculations in a previous information request (UARB IR-4 Attachment 11) and explains that Nova Scotia Power Inc. manages these costs by dispatching its generation fleet based on the most economic energy sources available as load fluctuates.

Question IR-12: Reference Page 19, Line 1-4
Question IR-12: Reference Page 19, Line 1-4 Provide a detailed explanation including references supporting the position that "natural gas prices most likely revert to higher levels", and in particular, what is meant by "higher levels" in t...

AI summary The regulator is seeking a detailed explanation and supporting evidence regarding the assertion that natural gas prices are expected to revert to higher levels. Specifically, the request asks for a precise definition of what constitutes 'higher levels' in terms of actual pricing, requiring the respondent to provide quantitative data or specific price points to support their forecasting position.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Response IR-12: (cont'd) Outlook now forecasts an average price of about $8.50 per MMBtu (at Henry Hub) for the first quarter of2007. DATE FILED: November 20, 2006 CME IR-12 Page 2 of2

AI summary In response to Information Request IR-12, CME provides a price forecast for natural gas. The outlook predicts an average price of approximately $8.50 per MMBtu at the Henry Hub for the first quarter of 2007.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-17: Reference Page 61, Lines 8-9 Provide NSPI's views of markets and expert information considered and relied upon. Response IR-17: The referenced lines state: "The Company mon...

AI summary In response to an information request, CME seeks clarification on the market data and expert information Nova Scotia Power Inc. (NSPI) relies upon regarding foreign exchange. NSPI clarifies that it monitors foreign exchange markets and consults with economists and currency experts in both Canada and the United States. NSPI further states that it consolidates market forecasts on a periodic basis, providing specific summaries in the referenced attachments.

FX Forecasts as of Sept, 2006
FX Forecasts as of Sept, 2006 2006 2007 2008 2009 Q4 Ql Q2 Q3 Q4 erne 1.13 1.15 1.14 1.15 1.15 1.12 1.12 BoA 1.11 1.13 1.14 1.16 1.17 RBe 1.17 1.19 1.21 1.24 1.24 1.26 1.28 BMO 1.13 1.15 1.15 1.13 1.14 TD 1.14 1.14 1.15 1.14 1.14 1.11 BNS...

AI summary The document presents a table of foreign exchange (FX) forecasts as of September 2006, covering the period from Q4 2006 through 2009. It provides specific exchange rate projections from several financial institutions, including BMO, BNS, BoA, CME, ELI, RBe, and TD, alongside an average forecast. These forecasts are used to project currency fluctuations relevant to the utility's financial planning and costs.

BMO Nesbitt Burns-
BMO Nesbitt Burns- Scotiabank Group - Although commodity prices have come off we expect stability and improvement in commodities to provide support to the CAD. If we enter a period of wavering global demand for the USD, Canada offers bette...

AI summary The text presents market outlooks from BMO Nesbitt Burns (Scotiabank Group) and CIBC World Markets regarding the Canadian Dollar (CAD). Scotiabank expects commodity price stability to support the CAD and suggests Canada offers better relative value than in previous months. CIBC World Markets notes that while M&A activity has impacted the CAD, healthy oil and base metal prices are expected to maintain Canada's trade surplus relative to a significant US deficit.

FX Forecasts as of Sept, 2006
FX Forecasts as of Sept, 2006 2006 2007 2008 2009 03 04 01 02 03 04 erne 1.09 1.13 1.15 1.14 1.15 1.15 1.15 1.15 BoA 1.12 1.08 1.06 1.06 1.08 1.11 RBe 1.13 1.17 1.19 1.21 1.24 1.24 1.21 1.19 BMO 1.12 1.11 1.09 1.09 1.12 1.14 1.15 1.18 BNS...

AI summary The document provides a table of foreign exchange (FX) forecasts for the Canadian Dollar (CAD) against the United States Dollar (USD) for the period of 2006 through 2009. It presents specific projections from several financial institutions, including Bank of America, Royal Bank of Canada, Bank of Montreal, and Bank of Nova Scotia, alongside a calculated average forecast. The data serves as an input for economic modeling and financial planning within the regulatory proceeding.

Section 63
Bank of America -Recent softer data and further implosion of oil and natural gas prices have not deterred CAD buyers. Look for at least some period of softness ahead. CAD continues to benefit from twin surpluses, terms of trade valuation a...

AI summary The text presents various financial forecasts for the Canadian dollar (CAD) based on commodity price trends, US economic growth, and capital flows. Bank of America and BMO Nesbitt Burns note a recent rally in the CAD despite softer oil and gas prices. Scotiabank Group expects medium-term strength due to investment inflows and a weak US dollar. Conversely, RBC Capital predicts a potential USD/CAD rally due to a projected US economic slowdown, while identifying M&A inflows and energy price volatility as key risks.

Section 64
ur forecast are (1) continued M&A inflows, (2) a mild or delayed slowdown in commodity prices, and (3) elevated energy prices due to devastating hurricanes and increased Middle East political tension. CIBC World Markets - Our call for a fm...

AI summary The text discusses economic forecasts for the Canadian Dollar (C$), citing three primary drivers: continued M&A inflows, a potential slowdown in commodity prices, and elevated energy prices resulting from hurricanes and Middle East tensions. Additionally, CIBC World Markets suggests a push toward the strong end of the trading range for the C$ due to soft US$ sentiment and a healthy trade balance, while advising an exit from long C$ positions in anticipation of disappointing growth and Bank of Canada rate cuts in 2007.

FX Forecasts as of June 9, 2006
FX Forecasts as of June 9, 2006 2006 2007 2008 2009 03 04 01 02 03 04 erne 1.09 1.13 1.15 1.14 1.15 1.15 1.15 1.15 BoA 1.12 1.08 1.06 1.06 1.08 1.11 RBe 1.15 1.17 1.19 1.21 1.24 1.24 1.21 1.19 BMO 1.10 1.09 1.07 1.09 1.12 1.14 BNS 1.08 1.0...

AI summary The document provides a table of foreign exchange (FX) forecasts as of June 9, 2006, comparing the Canadian Dollar to the United States Dollar. It lists specific exchange rate projections for various financial institutions—including Bank of America, Royal Bank of Canada, Bank of Montreal, and Bank of Nova Scotia—spanning the period from March 2006 through 2009, alongside an overall average forecast.

Section 66
Bank of America -Forecasting a general overall USD decline over the next 12 months. CAD to continue strong due to high commodity prices and current account surpluses. Expect CAD to eventually make new lows and there remains a very good cha...

AI summary The text presents various financial outlooks and forecasts for the Canadian Dollar (CAD) relative to the US Dollar (USD) from several major banking institutions. The consensus highlights factors supporting the CAD, including high commodity prices, current account surpluses, and solid economic growth. However, the institutions also identify risks such as potential US interest rate movements, global economic expansion (specifically in China), and geopolitical risks affecting oil prices, with specific targets for the CAD ranging between 92 cents and a forecast of 1.21 by Q2/07.

FX Forecasts as of May 2, 2006
FX Forecasts as of May 2, 2006 2006 2007 2008 2009 0 2 03 04 01 0 2 03 04 erne 1.11 1.13 1.15 1.17 1.18 1.20 1.20 1.20 1.20 BoA 1.13 1.12 1.10 1.09 1.10 1.12 1.15 RBe 1.13 1.15 1.17 1.19 1.21 1.24 1.24 1.22 1.20 BMO 1.12 1.10 1.08 1.06 1.1...

AI summary This section presents foreign exchange (FX) forecasts as of May 2, 006, comparing various projections for the Canadian Dollar against the United States Dollar. The data includes specific forecasts from major financial institutions, including Bank of America, Royal Bank of Canada, Bank of Montreal, and Bank of Nova Scotia, alongside an average forecast ranging from 1.11 to 1.20 over the 2006-2009 period.

Section 68
Bank of America -Forecasting a general overall USD decline over the next 12 months. CAD to continue strong due to high commodity prices and current account surpluses. BofC seems to be ok with the CAD at these levels. Political risk increas...

AI summary The text presents economic forecasts from four major financial institutions (Bank of America, BMO Nesbitt Burns, Scotiabank Group, and RBC Capital) regarding the Canadian Dollar (CAD) and US Dollar (USD) for 2006-2007. The consensus suggests a strengthening CAD driven by rising commodity prices, strong domestic economic data, and a potential pause in US interest rate hikes. Conversely, the USD is expected to weaken due to geopolitical tensions, central bank diversification, and slowing US economic growth relative to Canada.

Section 69
sted which will lead to an increased demand for CAD exports. For 2007 we are forecasting the US economy to grow at a slower rate than Canada. Historically this has been associated with a stronger CAD. CIBC World Markets -Strong commodity p...

AI summary The text discusses economic forecasts for 2007, focusing on the Canadian Dollar (CAD) and its relationship with the US economy. It highlights that while strong commodity prices support the CAD, a potential slowdown in the US economy and a weakening CAD could result from lower interest rates from the Bank of Canada. Additionally, it notes that continued job creation in resources, construction, and services is necessary to offset manufacturing job losses to sustain current currency levels.

2006 - 2009 USD Ex~osure FX Forecasts as of February 08, 2006
2006 - 2009 USD Ex~osure FX Forecasts as of February 08, 2006 2006 2007 2009 Ql 02 Q3 Q4 Ql Q2 Q3 Q4 2008 erne 1.13 1.10 1.13 1.15 1.18 1.20 1.20 1.20 BoA 1.15 1.13 1.11 1.09 1.08 1.10 1.12 1.15 RBe 1.17 1.19 1.21 1.22 1.22 1.23 1.24 1.22...

AI summary The document presents a table of foreign exchange (FX) forecasts for the Canadian Dollar (CAD) against the United States Dollar (USD) for the period between 2006 and 2009. It compiles various exchange rate projections from multiple financial institutions, including Bank of America, Royal Bank of Canada, Bank of Montreal, and Bank of Nova Scotia, alongside a calculated average. These forecasts were compiled as of February 8, 2006, to assess USD exposure.

Preamble
Bank of America- Conservative Government is generally CAD positive. However Harper eased exporters concerns by advocating that "a strong CAD did not necessarily mean a rising CAD". BoA remains CAD bullish for the remainder of the year. Nea...

AI summary The text presents various financial forecasts and analyses regarding the Canadian Dollar (CAD) and its relationship with the US Dollar (USD). Major financial institutions, including Bank of America, Scotiabank, RBC Capital, and CIBC World Markets, discuss factors influencing CAD strength, such as yield spreads, energy prices, twin surpluses, and the Bank of Canada's interest rate trajectory. While perspectives vary on the specific targets and duration of CAD strength, there is a general consensus on the impact of high energy prices and monetary policy on the currency's value.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-29: Reference Page 140, Lines 29-31 Adjusting for the re-entry of a large industrial customer, provide a detailed explanation including assumptions as to why load increases are...

AI summary Campbell Scott Management (CME) responds to an Information Request (IR-29) regarding Nova Scotia Power Inc.'s (NSPI) load growth forecasts. CME disputes the premise of the question, arguing that the projected load increases are consistent with historical patterns. To support this, CME provides a table estimating load growth rates that would have occurred if a specific large industrial customer had been at full load since 2006, demonstrating that the 2007 forecasts remain within historical ranges.

Residential Commercial Industrial Requirement
Residential Commercial Industrial Requirement Year GWh Growth GWh Growth GWh Growth GWh GWh Growth 2000 3,672 4.6% 2,829 2.3% 3,930 1.5% 809 11,240 3.4% 2001 3,741 1.9% 2,959 4.6% 3,873 -1.5% 730 11 ,303 0.6% 2002 3,829 2.3% 2,996 1.3% 3,7...

AI summary The document provides a historical breakdown of electricity consumption in Nova Scotia from 2000 to 2007, categorized by customer type: Residential, Commercial, and Industrial. It details annual consumption in Gigawatt-hours (GWh) and the corresponding growth rates for each sector. The data highlights varying growth trends, such as the Industrial sector's fluctuations and the specific inclusion of a Large Industrial Customer in the 2006 forecast.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-33a: Reference Page 151, Lines 17-21 and Page 152, Lines 1-5 Provide a detailed explanation and analysis as to the line losses. Response IR-33a: Forecast sales are divided by c...

AI summary Campbell Scott Management (CME) provided a detailed response to Nova Scotia Power Inc. (NSPI) regarding the calculation of line losses for the 2007 forecast. The response explains that losses are categorized into distribution and transmission. Distribution losses are calculated by applying a historical average loss percentage of 6.2% to forecast distribution sales. Transmission losses are calculated by applying a historical average loss percentage of 3.0% to the total transmission load, which includes distribution sales, distribution losses, and transmission sales.

Class 2006C GWh 2007 GWh Increase GWh Change o;o
Class 2006C GWh 2007 GWh Increase GWh Change o;o Residential 4,200 4,257 58 1% Small General 246 242 (4) -2% General Demand 2,472 2,479 6 0% Large General 426 421 (4) -1% Unmetered 110 112 3 2% Small Industrial 247 253 6 2% Medium Industri...

AI summary The document presents a table comparing electricity consumption in Gigawatt-hours (GWh) between 2006C and 2007 across various customer classes and categories. It shows slight increases in residential, small industrial, and large industrial sectors, while exports and GRLF saw decreases. The text notes that a detailed explanation of the 2007 forecast by sector is provided in Section 7.0 of the Direct Evidence.

N-2-eRIRs 1 to 49 - Liberty to NSPI - REDACTED (Large File - 15 MB) 4 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Liberty REDACTED Question IR-10: Please provide the current forecast of fuel burn levels for each generating station for 2006 through 2010. Include projections for each fuel type, MMBTU consum...

AI summary Nova Scotia Power Incorporated (NSPI) responded to an information request regarding fuel burn forecasts for generating stations from 2006 to 2010. NSPI provided specific data for 2006 and 2007 in confidential attachments and noted that it utilizes a consensus forecast method for determining test year fuel costs and revenue requirements. Additionally, NSPI provided an addendum regarding the portfolio requirement of solid fuel assets, noting that these assets are generally base-loaded and minimally affected by load changes.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Liberty Question IR-11: Please provide backup information for the 2007 forecast regarding the solid fuel commodity cost, transportation costs to move the coal to Nova Scotia, foreign exchange,...

AI summary Liberty provided a response to Information Request IR-11 regarding the 2007 solid fuel commodity cost forecast. The response directs the reviewer to specific attachments within IR-43 to find sourcing assumptions, a breakdown of major cost components by generating plant (in total dollars and $/MMBtu), fuel parameters for various solid fuels, and the calculation of plant-delivered costs used as inputs for the Strategist run.

Response IR-35 (cont'd):
Response IR-35 (cont'd): For the 2007 test year, NSPI used the forward price curve for HFO and natural gas adjusted for delivery costs, handling costs and foreign exchange rates. These fuel prices were entered in the Strategist model which...

AI summary Nova Scotia Power Incorporated (NSPI) describes its methodology for the 2007 test year regarding fuel procurement at the Tufts Cove generating station. The company utilized a forward price curve for Heavy Fuel Oil (HFO) and natural gas, adjusted for delivery, handling, and foreign exchange rates. These prices were integrated into the Strategist model to determine monthly fuel consumption for Units 1, 2, and 3, while identifying the remaining volume of contracted natural gas available for sale.

Question IR-44:
Question IR-44: Figure 2.2 of The Notice of Application and Direct Evidence of NSPI presents NSPI fuel costs per MWh for the years 2001 through 2007. Please provide the substantiating detail for the fuel costs for each of the years 2005, 2...

AI summary The regulator is requesting substantiating details from Nova Scotia Power Incorporated (NSPI) regarding fuel costs per MWh for the years 2005, 2006C, and 2007F. The request specifies a breakdown of components including import and domestic coal, pet-coke, oil, natural gas, purchased power, and transportation costs. Additionally, NSPI must demonstrate how the 2006 coal disallowance was factored in and correlate these historical figures with current and forecasted fuel and purchased power expenses.

N-2-fRIRs 50 to 81 - Liberty to NSPI - REDACTED (Large File - 16 MB) 3 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Liberty REDACTED Question IR-56: Please provide the Company's forecast of each of the same three components for each of the remaining months of 2006 and each of the months of 2007. Also, pleas...

AI summary The response to information request IR-56 provides forecasts for the remaining months of 2006 and 2007, with pricing dates based on forward curves as of August 31, 2006, and July 31, 2006, respectively. The forecasts are detailed in Confidential Attachments 1 and 14.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Liberty REDACTED Response IR-63: (Cont'd) Figure 2.3.2 Data are from an annual forecast which has not been revised since the data of the Application.

AI summary The response to an information request by Liberty REDACTED indicates that the data provided comes from an annual forecast that has not been updated since the Application's data date.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Liberty REDACTED Question IR-64: With respect to the Application, the discussion of solid fuels forecasting methodology on pages 56 and 57 is not consistent with the discussion on pages 33 and...

AI summary The response to an information request regarding inconsistencies in the forecasting methodology for solid fuels in the Application is marked as confidential. The request also asked for 'contemporaneous bids' and 'forward price curves' used in developing the 2007 solid fuels budget.

N-2-fRIRs 1 to 18 - MEUNSC to NSPI - REDACTED 6 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: MEUNSC Question IR-S: Reference: Direct Evidence Page 179, Lines 13-1S Please provide the individual utility determinants used in forecasting the Municipal Utility revenue. Individual utilitie...

AI summary The Maritime Energy Users Notice Committee (MEUNSC) responded to an information request from Nova Scotia Power Inc. (NSPI) regarding the utility determinants used in forecasting Municipal Utility revenue. The response clarifies that the data includes seven entities, noting that one specific municipality is split into two separate accounts to distinguish between transformer ownership credit and no transformer ownership credit, ensuring consistency across different information requests.

Response IR-7: (cont'd)
Response IR-7: (cont'd) b.-e. The revised Generation Replacement Load Following loss factor results from a change in the way in which the Additional Energy portion ofBowater's load has been displayed. Until 2005, this energy had been taken...

AI summary The respondent explains a revision in the Generation Replacement Load Following loss factor, which stems from a change in how Bowater's 'Additional Energy' portion is categorized. Previously priced at the Load Following rate, this energy was moved to the Large Industrial rate with the Interruptible Rider following a 2004 UARB decision. While the load was moved from the GRLF class to Mersey Rate energy for reporting purposes, the respondent clarifies that the overall loss percentage for the combined Below The Line industrial load remains unchanged.

Question IR-12: Reference: Direct Evidence, Cost of Service Study, Exhibit 9C
Question IR-12: Reference: Direct Evidence, Cost of Service Study, Exhibit 9C - a. Please provide the individual utility demands used in each of the 3 CP months for the Municipal category. Individual utilities can be identified as one thro...

AI summary The Information Request (IR-12) seeks detailed data regarding municipal utility demands for three specific CP months. The requester asks for individual utility demands, identifying them numerically to maintain confidentiality, or alternatively, the methodology used for co-incident peak estimates. Furthermore, the request asks whether these estimates account for specific variables such as weather conditions, cold load pick-up impacts, and municipal peak demand management efforts on both actual and forecasted levels.

Response IR-12
Response IR-12 - a. Load determinants used in the Cost of Service Study (COSS) are at the class level, not at an individual customer level. The coincident peak estimates are the class demands coincident at the time of system peak identifie...

AI summary Nova Scotia Power Inc. (NSPI) clarifies the methodology for determining load determinants in its Cost of Service Study (COSS). The company states that load shapes and coincident peak estimates are calculated at the class level rather than for individual customers. These class load shapes are derived from historical load research data, and any specific factors influencing load are accounted for based on historical occurrences within the test year.

Question IR-13:
Question IR-13: Reference: Direct Evidence Page 63, Lines 12-15 "Load growth has significantly increased the marginal cost of electricity and is responsible for a significant portion of overall fuel cost increases in 2007." (emphasis added...

AI summary The Information Request (IR-13) seeks clarification on the relationship between load growth and escalating electricity costs. Specifically, it requests details on efforts to mitigate these costs through demand-side management (DSM), energy conservation, and pricing strategies during the current test period. It further asks for projections on whether the 2% annual increase requirement will persist and requests identification of the primary sources driving current load growth.

Response IR-13:
Response IR-13: - a. Please refer to DARB IR-39b. - b. The forecast of annual demand and energy for 2007 to 2015 ts included in Appendix F of the Direct Evidence. - c. The major sources of load growth for 2007 are outlined by residential,...

AI summary The respondent provides a brief response to Information Request IR-13, directing the Board to previous filings (DARB IR-39b) for specific information. It notes that the annual demand and energy forecasts for 2007 to 2015 are located in Appendix F of the Direct Evidence, and identifies the primary sources of load growth for 2007 as being categorized by residential, commercial, and industrial sectors in Section 7.4 of the same evidence.

N-2-fRIRs 1 to 29 - SEB to NSPI - REDACTED 6 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Question IR-2: Please provide a breakdown of the increase in solid fuel costs from 2006 to 2007 by: a. petroleum coke; b. low sulphur coal; c. medium sulphur coal; d. high sulphur coal. Pl...

AI summary The System Evaluation Board (SEB) provided a response to an information request from Nova Scotia Power Inc. (NSPI) regarding the breakdown of solid fuel cost increases between 2006 and 2007. The response directs the reader to specific attachments for an analysis of petroleum coke and various sulphur coal types (low, medium, and high). It specifically highlights that a $15.7 million import coal disallowance from 2006 was arbitrarily allocated to the delivered price of 2006 forecast import coal costs.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Question IR-15: With reference to the consensus forecast referred to on page 57, please detail the different forecasts that have been used in producing the coal and pet coke price estimate...

AI summary The System Evaluation Board (SEB) provides a response to an Information Request (IR-15) from Nova Scotia Power Inc. (NSPI). The request asks for detailed particulars regarding the various forecasts used to estimate coal and pet coke prices for 2007. The SEB directs the respondent to Liberty IR-64 for the specific details requested.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB REDACTED Question IR-24: Response IR-24: Please refer to Liberty IR-43 Attachment 14 for the forward pricing data as of July 31, 2006, which is the forward curve date NSPI used to produce...

AI summary The System Evaluation Board (SEB) provided a response to Nova Scotia Power Inc. (NSPI) regarding Information Request IR-24. The response directs the reader to Liberty IR-43 Attachment 14 to find the specific forward curve date used by NSPI to generate the 2007 forecast for natural gas prices as of July 31, 2006.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Question IR-25: Please explain and reconcile the apparent difference between the monthly HFO and Natural Gas prices shown in Figure 2.6 and the seemingly lower prices for these fuels that...

AI summary The System Evaluation Board (SEB) requested a reconciliation between different price figures for Heavy Fuel Oil (HFO) and natural gas provided in the filing. Nova Scotia Power Inc. (NSPI) clarified that Figure 2.6 shows monthly market prices derived solely from forward curves without considering inventories or contracts. In contrast, Figures 2.7 and 2.9 reflect annual forecasted consumed prices, which incorporate opening inventories, financial hedges, contract pricing, and specific forecasted consumption volumes for various generating plants.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Response IR-25: (cont'd) Please refer to Liberty IR-43 Attachment 5 for the detailed calculation to support the 2006C forecasted price of natural gas as depicted in 2.9. Please refer to Li...

AI summary The System Evaluation Board (SEB) provides a response to Nova Scotia Power Inc. (NSPI) regarding Information Request IR-25. The response directs the reader to specific attachments within Liberty IR-43 to find detailed calculations supporting the forecasted prices of natural gas for the years 2006C and 2007, as illustrated in Figure 2.9.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB REDACTED Question IR-29: On page 57 the evidence states that Figure 2.10 is representative of various perspectives and is a consensus forecast. Please provide the minimum and maximum price...

AI summary The System Evaluation Board (SEB) responded to an Information Request (IR-29) from Nova Scotia Power Inc. (NSPI) regarding the methodology used for solid fuel price forecasting. The Board provided a Confidential Attachment containing the minimum and maximum price points for each type of solid fuel that were utilized to develop the consensus forecast presented in Figure 2.10 of the evidence.

N-2-fRIRs 1 to 10 - NSDOE to NSPI - REDACTED 3 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: NSDOE Question IR-1: The rate application requests rate adjustments to be effective April 1, 2007. Is the Test Year period Jan 1st, 2007 to Dec 31st, 2007 and if so please explain why the Test...

AI summary Nova Scotia Power Inc. (NSPI) clarifies that the test year for its rate application is January 1, 2007, to December 31, 2007, rather than a period starting April 1, 2007. The department explains that this calendar year alignment is consistent with past filings and is necessary because NSPI's financial and operating records, including tax and pension expenses, are reported on an annual calendar basis. This alignment facilitates transparency and easier comparison of financial data.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: NSDOE Question IR-4: With reference to Page 7, Figure 2.1, NSPI Direct Evidence. - a. What amount of the $19.6 million increase between 2006C and 2007F for fuel and purchased power for Load In...

AI summary The Nova Scotia Department of Energy (NSDOE) is requesting specific information from Nova Scotia Power Inc. (NSPI) regarding fuel and purchased power costs. The inquiry focuses on a $19.6 million increase between 2006C and 2007F attributed to Load Increase, specifically seeking to isolate the portion related to the Stora operating at full capacity in 2007. Additionally, NSDOE requests clarification on the recovery of these costs under current rates and an explanation for a $40.1 million increase in commodity costs relative to 2006.

Response IR-4:
Response IR-4: - a. None. The customer was included at full load in both 2006C and 2007F. The customer does not contribute to the increased sales forecast for 2007. - b. Please refer to CME IR-3. - c. Please refer to UARB IR-4 Attachments...

AI summary Nova Scotia Power Inc. (NSPI) provided responses to Information Request IR-4, clarifying that a specific customer was included at full load in the 2006C and 2007F forecasts and does not contribute to the increased sales forecast for 2007. The response also directs the reviewer to previous Information Requests (CME IR-3) and specific attachments related to the Utility Analysis and Rate Board (UARB) IR-4.

N-2-gRIRs 30 to 91 - SEB to NSPI - REDACTED (Large File - 29 MB) 1 passage
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Question IR-63: Please provide a version of Appendix A with the Forecast 2006 year (column (2)) replaced by a pro forma version that employs the most recent data and also assumes normal we...

AI summary NSPI is unable to provide a revised version of Appendix A with updated forecast data for 2006 due to the inability to retroactively determine changes in unit dispatch or fuel mix. The response refers to Liberty IR-73 for further information.

N-2-gRIRs 1 to 25 - Stutz to NSPI - REDACTED (Large File - 18 MB) 5 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Stutz Question IR-2: Reference DE, page 2, Lines 21 to 22 How much of the incremental $68.5 million in fuel and purchased power costs is due to the increase in generation assumed for 2007F? Pr...

AI summary The document is a response to an Information Request (IR-2) from a representative named Stutz addressed to Nova Scotia Power Inc. (NSPI). The inquiry seeks to quantify how much of an incremental $68.5 million in fuel and purchased power costs is attributable to the increase in generation assumed for the 2007F period. The response directs the requester to specific attachments (1 through 14) within the UARB IR-4 filing for the supporting calculations.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Stutz Question IR-10: Reference DE, page 45, Figure 2.4 Please explain why the Pet Coke positions drop substantially in 2007 and then rebound in 2008 to 2010. Response IR-10: The petroleum cok...

AI summary In response to an Information Request regarding Figure 2.4 in the Direct Evidence, the respondent explains the fluctuations in petroleum coke positions. The substantial drop in 2007 is attributed to petroleum coke being uneconomic compared to high sulphur coal due to record-high pricing. The forecasted rebound from 2008 to 2010 is based on the expected availability of incremental supply and a projected return to historical pricing, though the respondent notes these outcomes are uncertain.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Stutz Question IR-17: Reference DE, page 150, lines 10 to 13 Does NSPI have any evidence that the "large Industrial Customer" that shut down in 2006 will not shut down again in 2007. If so ple...

AI summary Nova Scotia Power Inc. (NSPI) responded to an Information Request regarding the operational status of a large industrial customer that closed in 2006. NSPI stated that the customer informed them of plans to operate at full production for the entire year of 2007. NSPI indicated they have no reason to believe the customer will cease operations again in 2007.

1.1 Background regarding Street Light Study
1.1 Background regarding Street Light Study 19 20 18 Street and Crosswalk Lighting rates were initially developed based on a Street/Crosswalk Lighting Study conducted in 1977. 22 23 24 25 26 27 28 29 30 31 21 Since 1977, rate adjustments h...

AI summary The text outlines the historical basis and structure of Street and Crosswalk Lighting rates in Nova Scotia, which were originally developed in 1977. It explains that while these rates are adjusted based on the overall average rate changes for the Unmetered Class, they comprise specific components: power and energy, maintenance, and capital charges. The document distinguishes between full charge rates and partial rates based on fixture ownership and maintenance responsibilities. Additionally, it clarifies the relationship between the general Cost of Service Study (COSS) and specific Street Lighting Studies regarding cost allocation and revenue/cost ratios.

5 4.2 Schedule 2 - Determination of Maintenance Costs by Fixture Type
5 4.2 Schedule 2 - Determination of Maintenance Costs by Fixture Type 6 7 8 9 10 11 12 13 14 15 16 17 18 The purpose of this schedule is to assign current maintenance costs to all lights containing a maintenance charge, based on the servic...

AI summary The document outlines the methodology for determining maintenance costs for various light fixtures. It explains that current maintenance costs are assigned based on the service life of lamp types and specific weighting factors relative to 1 OOW High Pressure (Intensity) Sodium lights. By applying these weights to the total number of lights and using forecasted 2006C street light operating expenses (including corporate overhead and pension costs), the calculation establishes the annual and monthly maintenance charges for each fixture type.

N-7-aRIRs 8 to 23 - HRM to NSPI - REDACTED 3 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: HRM REDACTED Question IR-9: (cont'd) revenues provided in response to HRM IR-4 results in effectively the same figures as in part (c) of this question. - e. Please explain why Exhibit SA in th...

AI summary The Halifax Regional Municipality (HRM) is seeking clarification from Nova Scotia Power Inc. (NSPI) regarding discrepancies in unmetered account data and street lighting analysis. Specifically, HRM is questioning the increase in unmetered accounts despite constant photocellactuated fixtures, requesting reconciliation of differing MW figures provided in previous information requests, and seeking the underlying engineering calculations, representative class curves, and specific test years for account reporting.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: HRM REDACTED Question IR-9: (cont'd) j. To what extent were photocell-actuated fixtures considered to be coincident with NSPI's system peak in December, January and February of the 2007 foreca...

AI summary The Halifax Regional Municipality (HRM) provided a response to an Information Request (IR-9) regarding the demand levels of photocell-actuated street and crosswalk lighting fixtures during peak winter months in the 2007 forecast test-year. The response clarifies that HRM's initial calculations omitted ballast losses, leading to discrepancies with NSPI's proof of revenue calculations. HRM confirms the projected growth of unmetered accounts and provides specific fixture counts for existing and new installations.

Response IR-9: (cont'd)
Response IR-9: (cont'd) fixtures will result in new unmetered service accounts. Miscellaneous other unmetered services will also experience new account growth expected from new cable power supply units, customer-owned outdoor signs, teleph...

AI summary Nova Scotia Power Inc. (NSPI) provides technical details regarding unmetered service accounts, specifically relating to street lights and other miscellaneous unmetered services like bus shelters and traffic control intersections. The response clarifies that account growth is expected from new installations. It also specifies that the energy and demand figures used in Exhibit 9A are based on a 2007 unmetered class curve, noting that winter system peaks occur in the evening, which influences the calculation of hourly average coincident demand.

N-7-aRIRs 27 to 39 - AEC to NSPI - REDACTED 3 passages
Question IR-27:
Question IR-27: Further to your responses to AEC IR's 1-4, please explain why NSPI's forecasts an increase in the proportion of revenue from the residential class in 2007. - a. Please explain why revenue from the residential class is predi...

AI summary The AEC is requesting a detailed explanation from NSPI regarding its revenue forecasts for the residential class for 2007. Specifically, the AEC seeks to understand the discrepancy between a projected increase in residential revenue and a concurrent projected decline in Nova Scotia's population. The request also asks for historical data on consumer classes and revenue from 1980 to 2000, as well as any underlying reports or data supporting these population and revenue trends.

Preamble
e. The following table was created from the Conference Board of Canada and Statistics Canada data. 1) Figures presented reflect whole numbers which may incur $0.1 M in rounding differences on some line items

AI summary The text serves as a preamble for a data table derived from the Conference Board of Canada and Statistics Canada. It notes that the figures presented are rounded to whole numbers, which may result in rounding differences of up to $0.1 million on certain line items.

Response IR-27: (cont'd)
Response IR-27: (cont'd) Year Quarter NS Population Year Quarter NS Population 2006.1 936,996 2011.1 934,906 2006.2 936,849 2011 .2 934,776 2006.3 936,743 2011 .3 934,642 2006.4 936,655 2011.4 934,504 2007.1 936,573 2012.1 934,363 2007.2 9...

AI summary The document provides a quarterly breakdown of the Nova Scotia population from 2006.1 to 2015.4. It notes that revenue generated from the residential class is driven by growth within the residential sector, as forecasted by Nova Scotia Power Inc. (NSPI), and by approved rates.

N-7-aRIRs - AVON [et al] to NSPI - RIR 67 to 76 - REDACTED 2 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Avon REDACTED a. DATE FILED: December 6, 2006 Question IR-74: Reference: Application, Page 8, Line 3 In 2007, load is forecast to be 1 percent higher than 2006c....This additional load adds mi...

AI summary Avon submitted a response to Information Request IR-74 regarding Nova Scotia Power Inc.'s (NSPI) load forecasts and fuel costs for 2007. Avon sought clarification on the specific gigawatt-hour (GWh) increase in load and the associated incremental fuel costs. NSPI responded that the actual load increase is 0.92% (118,889 MWh) rather than the 1% previously cited. NSPI also referenced a previous information request (Liberty IR-86) to address the specific costs of serving the additional load.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Avon Question IR-76: Please provide a schedule showing hourly hydro generation for 2005 and 2006 to date. Response IR-76: This confidential information can be viewed at NSPI offices. NSPI fore...

AI summary Avon responded to an information request (IR-76) from Nova Scotia Power Inc. (NSPI) regarding hourly hydro generation schedules for 2005 and 2006 to date. Avon stated that this specific information is confidential and can only be viewed at NSPI offices. Furthermore, the response clarifies that NSPI forecasts hydro generation using a Board-approved methodology based on a 23-year production average.

N-7-aRIRs 47 to 67 - CME to NSPI - REDACTED 9 passages
If Flatline Loadshape is used in Fuel Cost Determination
If Flatline Loadshape is used in Fuel Cost Determination Using a flat line load shape to calculate actual SEB related fuel costs for 2007, the true-up need only address any differences between the net credits paid to SEB and NSPI's net avo...

AI summary The text discusses the methodology for calculating fuel cost true-ups when a flat line load shape is utilized in fuel cost determination for 2007. It specifies that for load decrements, Nova Scotia Power Inc. (NSPI) would determine savings by comparing the Customer Baseline Loadshape (CBL) against actual loads using the same generation dispatch order as the 2P-RTP 20-minute-ahead marginal cost. For load increments, the calculation would focus on the actual incremental cost of serving load exceeding the CBL.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME REDACTED Response IR-48: (cont'd) NSPI will forecast the hourly cost of serving the total system load including SEB at their CBL and will compare it to the actual cost of serving the resul...

AI summary Nova Scotia Power Inc. (NSPI) describes the methodology for calculating true-up amounts related to the Electricity Load Impact 2P-R TP (ELI2P-RTP) tariff. The process involves forecasting the hourly cost of serving total system load, including the Customer Baseline Loadshape (CBL) for the Nova Scotia Electricity Board (SEB), and comparing it to actual costs. The analysis separates SEB and non-SEB loads to determine the cost of load deviations. NSPI estimates that true-up amounts for 2007 could exceed $4 million, which would otherwise require future cost recovery from customers.

If Flatline Loadshape is not used in Fuel Cost Determination
If Flatline Loadshape is not used in Fuel Cost Determination Failing to use flat line load shapes in calculating the fuel costs, or not providing for some other means of incorporating these costs into NSPI' s approved revenue requirement,...

AI summary The text addresses the regulatory requirement for including fuel costs in the true-up calculation if flat line load shapes are not utilized in the initial fuel cost determination. It asserts that if NSPI's approved revenue requirement does not account for these specific costs through an alternative mechanism, they must be captured during the true-up process to ensure accurate cost recovery.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME REDACTED Question IR-49: Reference CME – IR-12 What is the pricing of natural gas at the "floor level"? Also, provide data, consultants reports, industry and other economic outlooks, etc....

AI summary In response to an information request from Canadian Mineral Exploration (CME), the respondent explains that natural gas 'floor' pricing cannot be expressed as a single figure. Instead, the floor is reached when natural gas-fired electricity generation begins displacing significant coal-fired generation, making it dependent on regional coal prices and emission allowances. The response notes that short-term pricing is highly sensitive to weather conditions and cites a U.S. Energy Information Administration forecast projecting Henry Hub prices for 2007.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME REDACTED Response IR-49: (cont'd) A report published by the EIA Office of Oil and Gas in October 2006 addresses the relationship between crude oil and natural gas prices. 3 The authors fin...

AI summary In response to Information Request IR-49, CME references a 2006 report by the Energy Information Administration (EIA) regarding the correlation between crude oil and natural gas prices. The report concludes that while the prices of the two commodities have recently decoupled, a long-term relationship persists where significant, permanent increases in crude oil prices are expected to result in substantial increases in natural gas prices.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-53: Reference CA- IR-24 Considering that fuel procurement is based on a portfolio with varying terms, capital and other costs amortized over periods of time, etc., it is respec...

AI summary In response to an Information Request (IR-53) regarding the factors influencing fuel cost per MWh, Canadian Mineral Exploration (CME) requested details on how future fuel procurement terms, capital costs, and amortization might affect the 2007 test period. Nova Scotia Power Inc. (NSPI) responded by directing the reviewer to Section 2 of their Direct Evidence, 'Fuel and Purchased Power,' and stated that specific factors regarding future years will be addressed in subsequent applications as necessary.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-62: Reference UARB- IR-9 and CME- IR-6 Provide a further detailed explanation beyond the answer provided including a detailed breakdown explanation of the methodology of how NS...

AI summary Canadian Mineral Exploration (CME) provides a detailed explanation of Nova Scotia Power Inc.'s (NSPI) fleet dispatch methodology in response to an Information Request. The process utilizes the Strategist software's Generation and Fuel (GAF) module, which employs probabilistic production costing techniques. The methodology involves two stages: first, modifying system load shapes using data from the Load Forecast Adjustment module (including hydro generation and transactions); and second, simulating thermal unit operations by modeling capacity segments, must-run designations, and planned maintenance schedules.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Response IR-62: (cont'd) commitment criterion; that is a sufficient number of units are available to meet a user-defined percentage of the expected peak demand. Operationally, the commitme...

AI summary Canadian Mineral Exploration (CME) provides a technical explanation of the commitment criterion and dispatch costs within the Generation and Fuel (GAF) module. The response describes how units are brought online to meet peak demand requirements and explains the calculation of dispatch costs per MWh. This calculation involves multiplying the average heat rate by the fuel cost, adding variable operating and maintenance costs, and applying specific operating or loss factors to ensure economic dispatch of generating units.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: CME Question IR-66: Reference UARB- IR-44 The CME respectfully disagrees that forecasts of OM&G costs are not relevant to establishing the 2007 test year and asks that the question be fully an...

AI summary Canadian Mineral Exploration (CME) challenges Nova Scotia Power Inc.'s (NSPI) position regarding the relevance of Generation and Fuel (OM&G) cost forecasts for the 2007 test year. CME argues that 'initiatives foregone' impacts current and future test years, asserting that sophisticated organizations utilize multi-year plans and budgets despite inherent uncertainties. NSPI responds by stating they have already provided the requested information in a previous information request.

N-7-bRIRs 92 to 141 - SEB to NSPI - REDACTED (Large File - 11 MB) 4 passages
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB REDACTED Question IR-100: Taking account of all contracts entered into, contract revisions made, and options exercised (either to utilize the option or not), please provide NSPI's calculat...

AI summary Nova Scotia Power Incorporated (NSPI) responded to an information request regarding the impact of using specific external reports (Jacobs Consultancy and Hill & Associates) for 2007 solid fuel expense calculations. NSPI stated that using these forecasts would result in a fuel expense approximately $4 million (USD) lower than their own consensus forecast. NSPI argued that the reports do not reflect actual market prices, which were significantly higher for petroleum coke and high sulphur coal in 2007.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB REDACTED Question IR-104: In response to SEB IR-24, NSPI refers to forward pricing data as of July 31, 2006, which is the forward curve date NSPI used to produce the 2007 forecast natural...

AI summary Nova Scotia Power Incorporated (NSPI) responded to an Information Request from the Nova Scotia Utility and Review Board (SEB) regarding natural gas price forecasting. NSPI analyzed the impact of using forward pricing data from November 27, 2006, instead of July 31, 2006. The analysis indicates that while the updated data would decrease estimated fuel expenses by approximately $6.6 million for the 2007 projected gas burn, this benefit is largely offset by a $6.3 million decrease in resale margins.

Question IR-108: Please provide the following information:
Question IR-108: Please provide the following information: - a. The estimated total solid fuel cost (excluding petroleum coke) submitted in support of the 2006 test year rate review. In addition supply the total generation in MWh in 2006 a...

AI summary The document contains a formal Information Request (IR-108) and the corresponding response regarding solid fuel costs and generation levels. The inquiry seeks a comparison between estimated and actual costs for 2006 and 2007 test years, specifically distinguishing between costs that include and exclude petroleum coke. Nova Scotia Power Incorporated provided a detailed table of these costs and the associated generation levels in MWh for the requested periods.

RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Question IR-114: Please indicate the date on which NSPI received the Hill and Associates forecast? Response IR-114: NSPI received a spreadsheet of prices in June 2006. NSPI received online...

AI summary Nova Scotia Power Incorporated (NSPI) responded to an Information Request (IR-114) from the Nova Scotia Utility and Review Board (SEB) regarding the receipt of the Hill and Associates forecast. NSPI clarified that they received a spreadsheet of prices in June 2006, followed by online access to the complete 2006 Edition of the International Coal Trade report on September 6, 2006, and a hard copy during the week of September 18, 2006.

N-7-bRIRs 11 to 17 - NSDOE to NSPI - REDACTED 1 passage
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: NSDOE REDACTED Question IR-11: With reference to NSPI's response to Liberty IR-9, Attachments 1 & 2 The average marginal costs for 2006 and 2007 from the Strategist System Report are and respe...

AI summary The Nova Scotia Department of Energy (NSDOE) explains that the increase in average marginal costs between 2006 and 2007 was driven by two primary factors: rising fuel prices and increasing electricity load. The marginal cost represents the expense of producing the next MWh, which is typically served by the last units dispatched—predominantly heavy fuel oil, natural gas, and light oil. Higher fuel prices and the necessity of engaging more expensive, secondary units to meet incremental load both contributed to the cost rise.

N-18Direct Testimony - Nancy Brockway on behalf of the Consumer Advocate REDACTED (Large File - 37 MB) 1 passage
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: Consumer Advocate Question IR-2: Please provide a copy of any forecasts of fuel costs, and of revenue from export sales and gas sales, prepared by or on behalf of NSPI for fuel costs for any y...

AI summary The Consumer Advocate requested fuel cost forecasts and revenue from export and gas sales by NSPI for 2007–2011. NSPI responded that such information is not available, but provided three hypothetical fuel cost scenarios of $434 million, $484 million, and $534 million as part of a previous response to SEB IR-1.

N-30RIRs 1 to 15 [Only IR-15 Attachment] - Nancy Brockway (on behalf of Consumer Advocate) to NS Attorney General 4 passages
What is Not Regularly Counted and Reported Doesn't Get Attention
curity. Even economic growth itself may have a different impact on the rich than on the poor, and the changing composition of the GDP impacts lower income groups differently than higher income groups. Remarkably, even though this informati...

AI summary The text critiques the limitations of conventional economic indicators like GDP and provincial income averages, arguing that they fail to capture income inequality and the differing impacts of growth on various socioeconomic groups. It highlights a significant lack of timely, granular data from Statistics Canada regarding income distribution and unpaid work. The author contends that relying on skewed averages prevents a true understanding of whether economic growth actually improves the well-being of the poor or the general population.

Definitions
Definitions In the following analysis, disposable income refers to market income plus government transfers, minus taxes, and therefore represents the money actually available for household expenditures. Market income refers to earned incom...

AI summary The text provides formal definitions for economic indicators used in the report, specifically focusing on 'disposable income,' 'market income,' and 'government cash transfers.' It notes that all values are expressed in constant 1998 dollars to adjust for inflation. The report clarifies that data represents household averages across quintiles rather than individuals. Furthermore, it emphasizes that livelihood security is influenced by both real income and the cost of government services, and it defines 'poorest' and 'richest' based on the bottom and top 20% of income brackets.

Section 43
Income in Canada , Statistics Canada Cat No. 75-202, Table <sup>26 Calculated from average after tax income shares in Income in Canada , Statistics Canada Cat No. 75-202, Table 7.2, p. 109. <sup>27 Calculated from average after tax i...

AI summary The provided text consists of footnotes referencing data from Statistics Canada publication 'Income in Canada' (Cat No. 75-202). These footnotes specify that certain calculations regarding average after-tax income shares were derived from specific tables and pages within the publication.

REFERENCES
130, February 1999. Statistics Canada. CANSIM database 6967-6977 and 9219-9229 Selected Economic Indicators - GDP per Capita. Statistics Canada. CANSIM database 9940-9950 Consumer Price Index. Statistics Canada. Corak, Miles and Andrew Hei...

AI summary The provided text is a list of references from Statistics Canada, primarily focusing on economic indicators, income mobility, employment trends, and low-income measures in Canada. The citations include data on GDP per capita, the Consumer Price Index, wage gaps between age groups, self-employment dynamics, and various low-income cut-offs and measures from the late 1990s.

N-38RIRs 1 to 10 - Colin Gubbins (on behalf of Stora Enso/ Bowater) to NSPI - REDACTED 1 passage
Response:
Response: This information has been redacted and is only being provided to parties to the confidentiality undertaking. IR-6 Please provide a complete description of the forecasting methodology of the McCloskey Group and copies of all forec...

AI summary The response indicates that the information requested regarding the forecasting methodology of the McCloskey Group and related forecasts from 2005 to 2007 has been redacted and is only shared with parties under a confidentiality agreement.

N-40RIRs 1 to 13 - Dr. Alan Rosenberg [SEB] to NSPI 1 passage
Response to Question No. IR-8 (continued):
Response to Question No. IR-8 (continued): forecasting tendency in AE's forecast of Isolated Generation O&M costs. The Board notes that the forecast in 2005 is 13.1% higher than 2004 actuals. The Board is not persuaded that AE has provided...

AI summary The Board questions the accuracy of AE's 2005 forecast for Isolated Generation O&M costs and reduces it by 10% based on FIRM's recommendation. It also notes ATCO Pipelines' history of overforecasting and directs a 15% reduction in its 2003 and 2004 forecasts. The Board references standard normalization practices in utility regulation, citing 'Accounting for Public Utilities' by Hahne and Aliff.

N-40RIRs Attachment SEB-NSPI - 2d (Large File - 20 MB) 1 passage
ATTACHMENT A (continued)
ATTACHMENT A (continued) - ( 1) The Historical Energy Cost Period is the calendar year immediately preceding the filing year. - (2) The margins from sales transactions shall be treated in the following manner:

AI summary The provided text is a fragment of a regulatory attachment defining the parameters for calculating energy costs. It specifies that the 'Historical Energy Cost Period' is defined as the calendar year immediately preceding the year in which a filing is submitted. Additionally, it introduces the methodology for treating margins from sales transactions, though the specific treatment details are cut off in this excerpt.

N-40RIRs Attachment SEB-NSPI - 2a, pt. 4 (Large File - 19 MB) 1 passage
Preamble
Sharing Proportion is also illustrated in Table 1 above and is the symmetrical proportion of Deferred NPC Adjustment eligible for recovery from, or repayment to customers. The Sharing Proportion shall be layered to reflect a Customer Propo...

AI summary The text outlines the mechanics for the Deferred NPC Adjustment, specifically defining the 'Sharing Proportion' which divides adjustments between customers and the company. It specifies that no interest is deferred for the company's portion. Additionally, it describes the Revenue Variation Adjustment based on actual versus forecast kilowatt-hours sold in Wyoming and establishes a 'Symmetrical Interest' rule where interest is paid to the company on under-collections and to customers on over-collections of the deferred balance.

N-40RIRs Attachment SEB-NSPI - 2a, pt. 2 (Large File - 15 MB) 1 passage
Preamble
demand related allocation methodology approved or utilized in the Company's most recent retail rate case. Beginning January 1, 1998, and until changed by the Commission, this factor is 86.13 percent. - 42.3.4. The total annual Grand Gulf c...

AI summary The text outlines the methodology for allocating and recovering Grand Gulf demand-related costs for Arkansas retail customers. Costs are allocated based on revenue requirements approved in the most recent retail rate case, using a demand-related allocation factor of 86.13 percent (effective since 1998). Recovery mechanisms differ by customer size: customers with maximum demands below 100 kW recover costs via an energy rate adder, while other classes use a demand rate adder. An annual reconciliation process adjusts future recoveries based on net over or under-recoveries from the previous twelve-month period.

N-40RIRs Attachment SEB-NSPI - 2a, pt. 5 (Large File - 20 MB) 3 passages
Method of Calculation For Demand-Side Management Costs (DSM)
Method of Calculation For Demand-Side Management Costs (DSM) DSM = (DP - TU) \ AAF, where: - DP = Estimated costs of DSM resource contracts executed in connection with the Company's integrated resource planning process or as a result of a...

AI summary The text outlines the specific mathematical methodology for calculating Demand-Side Management (DSM) costs. It defines DSM as the product of the estimated costs of DSM resource contracts (DP) and the Average Annual Factor (AAF). It also provides a formula for the 'True-Up' (TU) amount, which adjusts for variances between actual DSM-related revenue received from the Power Purchase Cost Factor (PPCF) and the actual costs intended for recovery, to be conducted on an annual basis.

Method of Calculation For Renewable Energy Resources(RER)
Method of Calculation For Renewable Energy Resources(RER) RER = (ERC - TIJ) \ AAF: - ERC = Estimated costs of renewable energy resources in connection with the Company's integrated resource planning process or as a result of a Commission-a...

AI summary The document outlines the specific mathematical formulas and methodology for calculating Renewable Energy Resources (RER) costs within the electricity tariff. It defines the components for calculating the Adjusted Allocation Factor (AAF), which incorporates Estimated costs of renewable energy resources (ERC), True-Up amounts (TU) to reconcile variances between actual costs and revenue, Demand Allocation Factors (DE), Base Power Sales (BPS), and a scaling factor (S). These calculations are intended to determine the distribution of costs across major rate classes for cost recovery via the Power Purchase Cost Factor (PPCF).

Where:
Where: - P Estimated purchased power costs, exclusive of fuel, on an annualized basis to co generator in excess of the annualized amounts recovered in base rates. - AF = The demand allocation factor for each listed rate class used to alloc...

AI summary The text defines several variables and formulas used to calculate the Purchased Power Cost Recovery Factor (PCRF). It specifies how estimated purchased power costs (P) are handled for co-generators, the demand allocation factor (AF) based on the most recently approved cost-of-service study, and the calculation for a correction amount (CA) to address variances between actual allocated costs and revenues. It also identifies the estimated annual kilowatt-hour sales (ES) for the applicable year.

N-44RIRs 144 to 191 - SEB to NSPI - REDACTED (Large File - 10 MB) 1 passage
RESPONSE TO INFORMATION REQUEST
RESPONSE TO INFORMATION REQUEST TO: NSPI FROM: SEB Question IR-154: Reference, Final Report, page 7. The report identifies a "typical range" for both "a small utility" and "a mid-large utility". - a) Please provide a list of all the "small...

AI summary The Nova Scotia Energy Board (SEB) requested clarification from Nova Scotia Power Inc. (NSPI) regarding the methodology used by Accenture to categorize utilities as 'small' or 'mid-large' in a Final Report. NSPI responded that these categories are based on relative sophistication of capabilities rather than strict geographic limits. NSPI defined a small utility as having fewer than 500,000 customers and a mid-size utility as having between 500,000 and 1,500,000 customers.

N-46Rebuttal Evidence of NSPI - REDACTED (Large File - 31 MB) 3 passages
Forecasting
Forecasting In the October 10, 2006 Application, the fuel budget was developed using hedges extant as of combined with forecasts of pricing for the open fuel positions 6 . For that application NSPI revised its methodology for developing th...

AI summary The document discusses NSPI's methodology for forecasting fuel costs, including the use of a consensus forecast for solid fuel and forward price curves for HFO and natural gas. It also mentions objections from intervenors and criticisms of the Hill & Associates forecast by Dr. Raschke.

23 Avon Closing Submission PagelO
23 Avon Closing Submission PagelO 25 The Avon Closing Submission did not simply criticize the use of the Hill forecast. 26 As shown below (emphasis added), the Avon Closing Submission criticized the 27 use of any long-term forecasts and ev...

AI summary The Avon Closing Submission argues against the use of long-term forecasts for near-term coal commitments, citing EVA testimony that forward price curves may be more accurate. NSPI's consultants agree that shorter-term forecasts are generally more reliable than long-term ones.

Discount Rate
Discount Rate June 5.75% July 5.50% September 5.25% November 5.00% December 5.25% 2

AI summary The table shows the discount rates for different months, with rates ranging from 5.00% to 5.75%. These rates may be used in financial calculations or regulatory proceedings involving capital expenditures or financial instruments.

N-46Rebuttal Evidence of NSPI - Appendix A to J - REDACTED (Large File 27 MB) 9 passages
Gas Market Studies
ucturing the gas market in Ontario. The client is the Ontario Energy Board. Specifically, evaluated restructuring gas storage and gas system supply and the application of performance based ratemaking. - Mr. Crook directs ICF's ongoing mark...

AI summary The text outlines the expertise of Mr. Crook in gas market analysis and modeling. It highlights his use of the North American Natural Gas Analysis System (NANGAS) to evaluate gas storage, system supply, and performance-based ratemaking for the Ontario Energy Board. Additionally, it details his work for the Amir of Qatar regarding LNG import expansion, and his advisory role for the Government of the Bahamas in developing tax and fee structures for LNG terminals.

APPENDIXD
APPENDIXD Census dat a from the first 10 m onths of East South Central Mississippi 48 7,748 13,060 $782 4.90 5.99 5.,5 -61 East South Central TN Tennessee 85 1,993 27,659 $1,481 4.90 5.36 2 3.72 -31% _ West South Central Arkansas 32 31,364...

AI summary The provided text is a data table (Appendix D) containing demographic and economic statistics for various U.S. states and regions. It includes data points such as census data, population figures, and various numerical indicators across regions like the East South Central, West South Central, Mountain, and Pacific regions. The text does not contain narrative arguments, specific actors, or regulatory discussion beyond the raw data presented in the table.

The forecast unit price figure is based on actual costs for the period 2003-2005. The following table presents the actual annual vegetation cost and spans-addressed information.
The forecast unit price figure is based on actual costs for the period 2003-2005. The following table presents the actual annual vegetation cost and spans-addressed information. Year Distribution System Vegetation Management Cost Spans Add...

AI summary The document provides a historical analysis of distribution system vegetation management costs from 2003 to 2005 to establish a forecast unit price. It presents a table showing annual costs, spans addressed, and average costs per span, noting an average of $332 per span over that period. The author concludes that a system average figure of $325 per span is a reasonable basis for budget purposes, despite expected changes in the mix of vegetation work across different periods and regions.

Research Contributions In referreed journals
ics, 14, 745-756. - 14. Qin, Y.S. and Smit h, B. (2004) The likelihood ratio test for homogeneity in normal mixtures in the presence of a structural parameter. Stat. Sinica, 14, 1165-1177. - 15. Langley, J.M., Halperin, S.A. , Boucher, F.D...

AI summary The provided text is a list of academic references cited in a research contribution section. The citations cover diverse scientific fields including statistics (likelihood ratio tests, non-linear modeling), medicine (pediatrics, immunization, antibiotics), and industrial processes (brewing fermentations). These references appear to support the methodology or context of the proceeding but do not contain specific regulatory arguments or facts regarding Nova Scotia's utility regulations.

Refereed Journals
Refereed Journals - 1 R. Kulperger, "Parametric estimation for a simple branching diffusion process', Journal of Multivariate Analysis, 9, pp. 101- 115, (1979). - 2 R. Kulperger, "Brillinger type mixing conditions for simple branching diff...

AI summary The provided text is a bibliography of refereed journals focusing on statistical research, specifically regarding branching diffusion processes, stochastic processes, and regression analysis. The citations highlight various mathematical methods such as parametric estimation, mixing conditions, and goodness of fit tests conducted by researchers like R. Kulperger and P. Guttorp between 1979 and 1987.

Refereed Conference Proceedings
Refereed Conference Proceedings - 53 R. Kulperger, "Testing for nonlinear shifts in stationary ¢-mixing processes", In Time Series Methods in Hydrosciences, ed. A. El-Sharraawi and S. Esterby, Elsevier Pub. Co. , 37- 44 (1982). - 54 R. Kul...

AI summary This document chunk contains a list of refereed conference proceedings and academic publications authored by Reg Kulperger. The cited works cover topics such as nonlinear shifts in stationary processes, regression with dependent errors, central limit theorems, generating functions, and stochastic finance. The text also lists the author's research interests, which include stochastic processes, asymptotic methods in statistics, statistical inference, applied probability, and probability theory.

SOME RECENT COLLOQUIUM LECTURES
SOME RECENT COLLOQUIUM LECTURES - 1. Stochastic Competing Species and Prey Predator Models. IMS/ CRM Colloquium Series, at UQAM, September 30, 2005. - 2. Stochastic Competing Species Processes. Shandong University, Jinan, China. November 2...

AI summary This section of the document lists various colloquium lectures presented by Kulperger in late 2005. The lectures cover advanced mathematical and statistical topics, including stochastic competing species and prey predator models, stochastic competing species processes, and GARCH residual processes. The presentations were held at various international institutions, including UQAM, Shandong University, and Beijing Norma University.

Table 1. Comparison of Absolute Percent Difference Between AEO Reference Case Projections and Realized Outcomes
Table 1. Comparison of Absolute Percent Difference Between AEO Reference Case Projections and Realized Outcomes Average Absolute Percei nt Difference Variable AEO82 to AEO2000 AEO82 to AEO2001 AEO82 to AEO2002 AEO82 to AEO2003 AEO82:to AEO...

AI summary The provided text is a table titled 'Comparison of Absolute Percent Difference Between AEO Reference Case Projections and Realized Outcomes.' It quantifies the variance between the Annual Energy Outlook (AEO) reference case projections and actual realized outcomes across several years (AEO82 to AEO2005). The data covers consumption and emissions (energy, petroleum, natural gas, coal, electricity, and CO2), production levels, import/export figures, and economic variables including world oil prices, natural gas wellhead prices, electricity prices, and Gross Domestic Product.

Section 205
Source: Statistics in Table 1 are a summary of the calculations in Tables 2 through 18. The data in Tables 2 through 18 are based on the 1982 through 2004 Annual Energy Outlook projections. Historical data are taken from the Annual Energy...

AI summary The text describes the data sources and methodology for the statistics presented in several tables, which are derived from the 1982 through 2004 Annual Energy Outlook projections. It identifies the Department of Energy (DOE) and Energy Information Administration (EIA) as the primary sources for historical data. Additionally, it notes specific nuances regarding carbon dioxide emission projections, energy intensity evaluations, and the inclusion of combined heat and power (CHP) electricity generation in coal price projections starting in AEO2003.

Disclaimer: These summaries were generated by AI from the filings they describe. We take care to make them accurate, but errors are possible - and they aren't advice. Only the filings themselves are the record: if you're relying on something here, confirm it against the source documents or the Nova Scotia Energy Board's own record. Full disclaimer →