3.4. Bottom Brook Converter and Switchyard Site - The facilities have been well maintained and are in good order. - Reactor hall door experienced heat induced buckling that initiated a 'door open' trip. Solutions to improve reliability of...
AI summary The Bottom Brook Converter and Switchyard Site facilities are in good condition, though a reactor hall door issue caused a trip. Solutions are being explored to improve reliability. The SPS installation is complete, and new GIC sensors have been installed to monitor GIC effects on the converter transformer fleet.
4. MARITIME LINK UPDATE SUMMER 2025 Update meeting was held at the Bottom Brook converter station in conjunction with IE site visit. Emera management and Natural Resources representatives joined the meeting virtually. - a) Safety - No issu...
AI summary An update meeting was held at the Bottom Brook converter station, with no safety issues identified. Helicopter patrols and drone inspections are planned for 2025 to inspect HVDC lines and transmission structures. A drone inspection found a shackle bolt issue on the OPGW wire, which was repaired. A wildfire crossed TL 269 but caused no visible damage.