BACK SPAN CONCERNS This discussion has focused only on the main span. Vibration of conductors such as experienced on this crossing is not limited to a single span. The motions are fed through the suspension clamps to the adjacent span that...
AI summary The discussion highlights concerns regarding the vibration of conductors on the new Canso Strait 230 kV crossing, emphasizing the need to inspect back spans and adjacent structures for damage. It also critiques Salvi's new damping scheme for being insufficient in frequency range and suggests using airflow spoilers from the old crossing for better protection.