Table 6: Voltage Limit Default Settings – from Table 10, CSA C22.3 No. 9 Function Voltage (% of nominal voltage) Clearing Time (sec) OV3 >120 0.16 OV2 > 110 2 OV1 > 106 120 UV1 < 88 10 UV2 < 45 0.16 Voltage ride-through performance require...
AI summary Table 6 outlines voltage limit default settings based on CSA C22.3 No. 9, specifying voltage thresholds and clearing times for various conditions. Inverter-based generation must meet voltage ride-through performance requirements as detailed in Table 7, ensuring continued connection to the distribution system within specified voltage-time ranges.