NON-CONFIDENTIAL 1 (b) The feeders identified as problem feeders in M12185 were not selected because the impact 15 remains effective regardless of the outage cause, and is cost-effective. 16 17 (b) NS Power does not have access to this lev...
AI summary The document discusses the implementation of FLISR schemes and their benefits, including cost-effectiveness, reduced manual switching, and lower GHG emissions. It notes that NS Power lacks detailed data on feeder performance and that FLISR benefits are well-established in comparable utility implementations.
NON-CONFIDENTIAL Feeder Circuit or FLISR Type Average Outage Duration (> 100 cust) [hrs] FLISR Restoration Time (min) Average FLISR (10-25%) Reduced Outage Duration [hrs] 85S-401 4.6 1 3.8 11S-411 3.6 1 3.0 Centralized 2.7 10 2.3 Decentral...
AI summary The document presents data on feeder circuits and FLISR types, including outage durations, restoration times, and associated operational costs. It highlights potential avoided operational costs from implementing FLISR systems, which could offset project costs over five years and improve feeder reliability.