NON-CONFIDENTIAL Cold Season Rating Protection Limit SCADA Alarm Limit 20 telemetry LIIR customer interruption. NS Power's ten-minute reserve dropped to 140 MW below 21 the required level, so even with all available generation resources in...
AI summary During a cold-weather event from January 23-26, 2026, wind generation dropped significantly due to decreasing wind speeds. There were no operational issues with the wind turbines, and the low production was attributed to low wind conditions rather than turbine performance issues.
Request IR-16: Page 20 of 23, Figures 11 and 12 provide hourly average wind generation and forecasts. (a) Please confirm whether the generation forecast was adjusted for cold weather. (i) If not, please provide Figure 11 and Figure 12 with...
AI summary The response to Request IR-16 explains that a temperature-adjusted generation forecast was not prepared for the January 2026 event, as temperatures were not expected to drop below -15°C. However, NS Power reconstructed a forecast based on available weather data, noting that some wind farms may experience reduced output in extreme cold.
Date: Sun January 25, 2026 HOUR LOAD FORECAST RESERVE REQMT SYSTEM MARGIN PA1 LIN1 LIN2 LIN3 LIN4 TR5 TR6 PT2 TUC1 TUC2 TUC3 TUC6 CT TOTAL IPP TOTAL PT BIO HYDRO TOTAL BESS WIND TOTAL FIRM NB PURCH FIRM NFLD PURCH 21 2287 218 -162 165 148...
AI summary The document presents a detailed table of hourly load forecasts, reserve requirements, and system margins for a specific date, along with various power generation and transmission metrics. It includes data on different power sources such as battery energy storage systems (BESS), wind, and hydroelectric generation, as well as firm purchases from New Brunswick and Newfoundland.